Foglio istruzioni
ed avvertenze
Warning and
instruction sheet
IT
IE
COD. 3.023314
KIT TERZA ZONA
AGGIUNTIVA
MAGIS HERCULES ERP
MAGIS HERCULES ERP
THIRD ZONE
ADDITIONAL KIT

Advertisement

loading
Need help?

Need help?

Do you have a question about the 3.023314 and is the answer not in the manual?

Questions and answers

Summary of Contents for Immergas 3.023314

  • Page 1 COD. 3.023314 KIT TERZA ZONA Foglio istruzioni ed avvertenze AGGIUNTIVA MAGIS HERCULES ERP MAGIS HERCULES ERP Warning and instruction sheet THIRD ZONE ADDITIONAL KIT...
  • Page 2: Avvertenze Generali

    AVVERTENZE GENERALI. L'installazione e la manutenzione devono essere effettuate in ottem- peranza alle normative vigenti, secondo le istruzioni del costruttore e Tutti i prodotti Immergas sono protetti con idoneo imballaggio da da parte di personale abilitato nonché professionalmente qualificato, trasporto.
  • Page 3 INSTALLAZIONE IDRAULICA. - Collegare in sequenza partendo dal tubo mandata impianto terza zona (13), circolatore (11), valvola miscelatrice (4) e tubo - Smontare la mantellatura della caldaia. (7) avendo cura di interporre le guarnizioni di tenuta come - Svuotare l’impianto di caldaia agendo sull’apposito raccordo di rappresentato in Fig.
  • Page 4 Composizione kit: Rif. Qtà Descrizione Rif. Qtà Descrizione Viti fissaggio termostato sicurezza Valvola miscelatrice Motore valvola miscelatrice Termostato sicurezza Dadi ribassati 3/4'' Coperchio motore valvola miscelatrice Raccordi tubi allacciamento 3/4'' Tubo ritorno zona 3 miscelata Guarnizioni 30x22x2 Guarnizioni 34x27x2 Guscio coibentazione circolatore Sonda mandata Guscio coibentazione valvola Guarnizioni 24x16x2...
  • Page 5: Schema Idraulico

    PRESCRIZIONI PER L’INSTALLAZIONE ELETTRICA. 2) Collegare il cavo per circolatore 3° Zona miscelata; I cavi di collegamento ai termostati ambiente (24V) e/o i cavi di 3) Inserire la fascetta che lega i due cavi. comunicazione dei controlli remoti zona non devono mai essere 4) Collegare i 2 connettori alla sonda di mandata e al connettore accoppiati a cavi di linea 230V.
  • Page 6 SCHEMA ELETTRICO COLLEGAMENTI.
  • Page 7 SCHEMA ELETTRICO ALLACCIAMENTI. Legenda: A16-3 - Deumidificatore zona 3 (optional) S20-3 - Termostato ambiente zona 3 (optional) S36-3 - Umidostato ambiente zona 3 (optional) Note: 29-x / 30-x: Comando Deumidifica in aria neutra; 31-x / 32-x: Comando Deumidifica in aria raffrescata; 33-3 / 34-3: Allarme Deumidificatore zona 3 (optional).
  • Page 8 POMPA DI CIRCOLAZIONE CIRCUITO IMPIANTO - Prevalenza proporzionale (ΔP V) (Rif. 3 Fig. 7). Consente di RAFFRESCAMENTO E RISCALDAMENTO (REGOLAZIONE ridurre proporzionalmente il livello di pressione (prevalenza) CON SELETTORE A MANOPOLA). al diminuire della richiesta da parte dell’impianto (riduzione I circolatori sono equipaggiati con un’ e lettronica di comando che della portata).
  • Page 9 POMPA DI CIRCOLAZIONE CIRCUITO IMPIANTO Altre funzioni: RAFFRESCAMENTO E RISCALDAMENTO (REGOLAZIONE - La funzione di sfiato della pompa si attiva premendo a lungo CON SELETTORE A PULSANTE). (3 secondi) il tasto di comando (Rif. 1 Fig. 9) ed esegue auto- Le caldaie vengono fornite con 2 circolatori entrambi muniti di maticamente lo sfiato della pompa.
  • Page 10 Guasti, cause e rimedi circolatore impianto. Guasti Cause Rimedi Fusibile elettrico difettoso Controllare i fusibili Pompa non funzionante con ali- mentazione di corrente inserita. La pompa è priva di tensione Eliminare l'interruzione dell'alimentazione di tensione Aumentare la pressione del sistema entro in campo consentito Cavitazione a causa di una pressione di La pompa genera dei rumori.
  • Page 11: General Warnings

    With this kit an independent mixing temperature zone is added This instruction manual provides technical information for installing (third zone). the Immergas kit. As for the other issues related to kit installation Before performing any intervention, remove the power supply (e.g. safety in the work site, environment protection, injury...
  • Page 12: Hydraulic Installation

    HYDRAULIC INSTALLATION - Connect in sequence starting from the third zone system flow pipe (13), circulator (11), mixing valve (4) and pipe (7), making - Remove the boiler casing. sure that the gaskets are placed as shown in Fig. 2. - Empty the boiler system by acting on the relevant drain Attention: respect the orientation of the mixing valve, as fitting positioned on the boiler return pipe in the lower part...
  • Page 13 Kit composition: Ref. Qty Description Ref. Qty Description Safety thermostat fixing screws Mixing valve Mixing valve motor Safety thermostat 3/4'' lowered nut Mixing valve motor lid 3/4'' connection pipes fitting Third zone mixing system return pipe 30x20x2 gaskets 34x27x2 gaskets Circulator insulation shell Flow probe Valve insulation shell...
  • Page 14: Hydraulic Diagram

    PROVISIONS FOR ELECTRIC INSTALLATION. 1) Connect the mixing valve cable. The connection cables to the room thermostats (24V) and/or the 2) Connect the 3rd mixing zone circulator cable. zone remote control communication cables must never be coupled 3) Insert the cable tie that ties the two cables. to 230V line cables.
  • Page 15: Internal Wiring Diagram

    INTERNAL WIRING DIAGRAM.
  • Page 16 WIRING DIAGRAM WITH CONNECTIONS. Key: A16-3 - Zone 3 Dehumidifier (optional) S20-3 - Zone 3 Room Thermostat (optional) S36-3 - Zone 3 Room Humidostat(optional) Notes: 29-x / 30-x: Dehumidification; 31-x / 32-x: Dehumidification with Cooling; 33-3 / 34-3: Zone 3 Dehumification Alarm (optional).
  • Page 17 CIRCULATION PUMP SYSTEM CIRCUIT COOLING - Proportional head (ΔP V) (Ref. 3 Fig. 7).This allows the pres- AND HEATING (ADJUSTMENT WITH KNOB SELECTOR sure level (head) to be proportionally reduced as the system SWITCH). heat demand decreases (flow rate reduction). Thanks to this The circulators are equipped with electronic control that allows to function, the electric power consumption of the circulator set advanced functions..
  • Page 18 CIRCULATION PUMP SYSTEM CIRCUIT COOLING AND Other functions: HEATING (REGULATION WITH BUTTON SELECTOR - The vent function of the pump is activated by pressing and hol- SWITCH). ding (3 seconds) the control key (Ref. 1 Fig. 9) and automatically The appliances are supplied with two circulators both equipped venting the pump.
  • Page 19: Troubleshooting

    Troubleshooting. Faults Causes Solutions Faulty electrical fuse Check the fuses Pump not working with power supply on. The pump is without voltage Eliminate the power supply cut-off Increase the system pressure within the allowed field The pump generates noise Cavitation due to insufficient flow pressure Check the head setting and eventually set a lower head Increase the delivery value The building does not heat up.
  • Page 20 Il libretto istruzioni è realizzato in carta ecologica. This instruction booklet is madeof ecological paper. immergas.com Per richiedere ulteriori approfondimenti specifici, i Profession- isti del settore possono anche avvalersi dell’indirizzo e-mail: consulenza@immergas.com Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617 SISTEMA DI QUALITÀ CERTIFICATO...