SystemAir SAVE VTR 150/B R 1000W User Manual page 28

Table of Contents

Advertisement

Available languages

Available languages

GB
Alarm name
CO₂
RH
Output in manual mode
Alarm Fire Alarm can be only activated with a digital signal from a smoke/fire detection system or similar. Digital in-
put has to be configured as Fire Alarm for this alarm to work.
Digital output configured as Sum Alarm sends a generic signal every time the alarm is triggered, except for alarms Ex-
ternal stop, Output in manual mode and Manual Fan Stop. This signal does not specify the alarm type.
212025 | A003
Explanation
External CO
sensor malfunction.
2
External relative humidity sensor
malfunction.
One or more of analogue outputs are
in manual mode.
Alarms |
Do the following
Check that sensor is connected
properly and cable is not damaged.
In case sensor wireless – check
RS485 gateway status and sensor
status in HMI.
Contact your installation company or
place of purchase.
Check that sensor is connected
properly and cable is not damaged.
In case sensor wireless – check
RS485 gateway status and sensor
status in HMI.
Contact your installation company or
place of purchase.
Check Service menu for Output
settings, and check all configured
outputs to be in Auto mode. If any
outputs in Manual - change back to
Auto mode.
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Save vtr 150/b

Table of Contents