Honeywell S7800A1142 Manual page 39

Keyboard display module
Hide thumbs Also See for S7800A1142:
Table of Contents

Advertisement

Device Address and Baud Rate
Assign each device in the system a unique address by setting the
MODBUS ADDRESS (see page 26). Only RTU communications
with 1 Start Bit, 8 Data Bits, 1 Stop Bit and no parity is supported.
NOTE: Assign a device address number from 01 to 99. 00 is
not an acceptable address number and will not work,
except for the broadcast ability of function 6.
Address
Register
(hex)
(dec)
0000
40001
Burner Control (BC) Fault Code R
0001
40002
BC Fault String Code
0002
40003
BC Sequence State
0003
40004
BC State String Code (line 1) R
0004
40005
BC State String Code (line 2) R
0005
40006
BC Sequence time
0006
40007
BC Total cycles
0008
40009
BC Total hours
000A
40011
BC Flame 1 signal strength
000B
40012
BC Flame 2 signal strength
000C
40013
BC State Bits
000D
40014
S7830 First Out Code
000E
40015
S7830 State Bits
0010-
40017-
BC Fault history record 1
0019
40026
001A-
40027-
BC Fault history record 2
0023
40036
0024-
40037-
BC Fault history record 3
002D
40046
002E-
40047-
BC Fault history record 4
0037
40056
0038-
40057-
BC Fault history record 5
0041
40066
0042-
40067-
BC Fault history record 6
004B
40076
004C
40077
BC Flame Failure Response
Time
004D
40078
BC Manufacturing code
004F
40080
BC Type Code
0050
40081
S7800M/BC Software version R
0052
40083
EA Software version
0054
40085
BC Remote Command status. R
0055
40086
BC Flame Amplifier type
0056
40087
BC Purge Time
0057-
40088-
BC Diagnostics
0065
40102
0066
40103
Post-Purge time
Table 17. ModBus™ Register Assignments.
Read/
Parameter Name
Write Format
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
7800 SERIES S7800A1142 KEYBOARD DISPLAY MODULE
NOTE: In Tables 10, 15 and 18: Line 1 and Line 2 refer to the
two lines of text on the S7800 Keyboard Display Mod-
ule. In Tables 21, 23 and 24: The String Code column
references Table 21, String Codes. In Table 22: The
Burner Control State Bits column references Table
21, Burner Control State Bits..
U16
See Table 23. Non-zero value = Lockout number.
U16
See Table 22. Lockout text.
U16
See Table 23 (valid only if Fault code = 0).
U16
See Table 22. Simulates Line 1 of S7800.
U16
See Table 22. Simulates Line 2 of S7800.
U16
0-4095 Seconds.
U32
Max value is 0xFFFFFFFF.
U32
Max value is 0xFFFFFFFF.
U16
0 to 255 represents 0.0 to 25.5 volts. Not clipped to 5.0V like
S7800.
U16
0 to 4095. N/A for 7800 SERIES.
U16
See Table 20.
U16
Not supported from S7800.
U32
Newest fault record. See Table 24.
Second newest fault record. See Table 24.
Third newest fault record. See Table 24.
Fourth newest fault record. See Table 24.
Fifth newest fault record. See Table 24.
Oldest fault record. See Table 24.
U16
Tenths of Seconds.
U32
U16
See Table 19.
U32
U32
Does not apply.
U16
Bit 0: Autonomous.
Bit 1: Remote commanded off.
Bit 2: Remote commanded High fire.
Bit 3: Remote commanded low fire.
Bit 4: Remote reset has/will be sent to BC.
Bits 5-14: Unused.
Bit 15: Copied after the most recent write to the burner
control command (40128 bit 15).
U16
0 = Standard
1 = Unknown
2 = Amplicheck or missing amplifier
3 = Shutter
U16
Seconds
U16
String codes indicating terminal/jumper state. See Table 20. There
are up to 15 codes. Not all are used for some burner controls.
U16
Seconds
39
Notes