Z dimensions
3.3.3

Required tools

Geopress K repair coupling
Minimum distances to underground pipelines and objects:
0.2 m to parallel supply lines
n
0.1 m to crossing pipelines
n
Alternatively, use insulating materials, to prevent pipelines that cross
each other from touching.
0.4 m to parallel cables over 1 kV
n
0.4 m to foundations or similar constructions
n
In the case of a distance < 1 m, the drinking water pipeline must not
n
be lower than the wastewater pipe.
For the Z dimensions, refer to the respective product page in the online
catalogue.
The following tools are required for production of a press connection:
pipe cutter, pipe shear or saw
n
deburrer and coloured pen for marking
n
battery-powered press machine
n
hinged adapter jaw model 2296.2
n
Z2 with 32–63 mm diameter
press ring model 9796.1
n
Handling