Important Safeguards - ABB EMIU 1500W Instruction Manual

4 option mini inverter
Hide thumbs Also See for EMIU 1500W:

Advertisement

THIS UNIT CONTAINS A
RECHARGEABLE VALVE-REGULATED
LEAD ACID BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS
THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM
BEFORE CONTACTING TECHNICAL SUPPORT MAKE SURE TO FOLLOW ALL STEPS IN SEQUENCE AND REFER TO
THE TROUBLESHOOTING GUIDE INCLUDED IN THIS MANUAL.
1. Install in accordance with the National Electrical Code and local regulations.
2. The EMIU contains potentially hazardous voltages. Installation, maintenance and service work should be performed by qualified
and trained personnel.
3. Units to be installed only as per configuration described in this instruction manual.
4.
Electricians and end-users need to ensure product system compatibility before final installation.
5. The AC voltage rating of this equipment is specified on the product label. Do not connect the EMIU equipment to any other voltage.
6. All unused wires must be capped to prevent shorting.
7. The EMIU should be mounted securely and in locations and at heights where it will not be readily subjected to tampering by
unauthorized personnel.
8. The use of accessory equipment and replacement parts not recommended by manufacturer may cause an unsafe condition and will
void the warranty.
9. Do not mount near gas or electric heaters.
10. Do not let power supply cords touch hot surfaces.
11. Do not use this equipment for other than its intended use.
12. DO NOT USE OUTDOORS.
13. The EMIU uses sealed valve regulated lead acid batteries. Batteries can be punctured if not handled properly, therefore use caution
when servicing batteries. In the event battery acid comes in contact with eyes or skin, flush with fresh water and consult a physician
immediately.
MODEL NUMBER
EMIU1500
120/277 VAC, 60Hz
NOTE: At 120Vac, unit is rated at power factor 0.8. For loads having a power factor below 0.8, unit capacity needs to be derated.
At 277Vac, unit is rated at unity power factor. For loads having a power factor below 1, unit capacity needs to be derated.
All ABB inverter products receive 100% quality inspection before shipment to ensure proper and satisfactory operation.
When operated under normal conditions, ABB inverter products will provide years of dependable service.
For the complete warranty information, please refer to the landing page of our website (http://www.emergi-lite.com/usa/).
Tel: (888) 552-6467

IMPORTANT SAFEGUARDS

SAVE THESE INSTRUCTIONS
AC SPECS
17.6 / 6.3 Amps
WARRANTY
Fax: (800) 316-4515
EMIU 1500W Mini Inverter
INTERRUPTIBLE EMERGENCY LIGHTING
UNIT INVERTER INSTRUCTION MANUAL
EMERGENCY POWER AVAILABLE FOR LOAD
90 MIN
2H
1500W
1136W
EMIU 1500W Mini Inverter
APPROX.
WEIGHT
3H
4H
789W
673W
395lbs.
11/22 750.2189 Rev. B
1/12