Page 1
KeContact E10 Smart Energy Meter IP Configuration guide V 1.01...
Page 2
Specifications are subject to change due to further technical developments. Details presented may be subject to correction. All rights reserved. Reindlstraße 51, 4040 Linz, Austria, www.keba.com/emobility KEBA Energy Automation GmbH +43 732 7090-0, +43 732 7309-10, kecontact@keba.com For information about KEBA and our subsidiaries please look at www.keba.com.
Introduction E10 Smart Energy Meter Introduction This manual is valid for KeContact E10 energy meters. Purpose of the document This document is an extension to the product installation manual. It de- scribes the additional installation work regarding the IP address assignment of the KeContact E10 energy meter.
It is recommended that the KeContact E10 gets a fixed IP address (IP-bind- ing) via the DHCP server (router, WLAN modem,…) of your local network. Access your DHCP server and set a fixed IP address for the KeContact E10. To do this, please refer to the manual of your router.
5) Enter “E10” in the text filter field (3). The current IP address of your KeContact E10 should show up (4). If it does not, please restart and / or reset your KeContact E10 as described in the Ke- Contact E10 Installation manual).
Set a fixed IP address for your Energy meter Set a fixed IP address for your Energy meter If it is not possible to set a fixed IP address for the KeContact E10 via your DHCP-server (IP-binding), please follow these instructions.
Page 8
1) Enter 259 in the Register field and click “Transmit packet”. This should show the first value of the currently set IP address. If an error is shown, check if the IP address of the KeContact E10 is correctly set. If not restart and / or reset the KeContact E10.
Page 9
Modbus Mechanic - manually set a new IP address 1) Open the tool and enter the IP address previously shown in the “Ad- vanced IP Scanner” tool for the KeContact E10 into the field “IP”. 2) Also enter Port „502“ and Node „1“.
Page 10
1) Important: Disable DHCP by changing Register 267 to value “0”. This will permanently set the IP address to the selected value. 2) Restart the KeContact E10 either via the reset button or changing Regis- ter 61615 to value “1”.
Page 12
KEBA Energy Automation GmbH Reindlstraße 51 4040 Linz / Austria www.keba.com...