Carrier 50FC 04 Series Service And Maintenance Instructions page 7

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 3 to 6 nominal tons
Hide thumbs Also See for 50FC 04 Series:
Table of Contents

Advertisement

Units with SystemVu
controls
On units equipped with the factory-installed SystemVu controller
the Fan Speed settings are accessed through the SystemVu
interface.
1.
Check the job specifications for the cfm (cubic feet per
minute) and ESP (external static pressure) required.
2.
Using the chart on the Fan Speed Set Up labels (see Fig. 9),
calculate the rpm from the cfm and ESP for the base unit.
3.
If installing any accessories listed at the bottom of the Set Up
Label, add accessory rpm to base unit rpm in upper portion of
label. For electric heaters use only one adder (e.g., 2 stage
heater uses only 2 stage adder, not 1 stage plus 2 stage).
NOTE: The Fan Speed Set Up labels are located on the High Volt-
age cover in the Control Box.
4.
Press any key on the SystemVu interface to activate the
display backlight and then press the MENU key.
5.
Using the UP and DOWN arrow keys highlight SET-
TINGS and then press ENTER.
RPM
Field Accessories:
1 Stage E Heat
2 Stage E Heat
NOTE: Values in the Field Accessories section are vdc adders.
Fig. 9 — Example of Fan Speed Set Up Labels for SystemVu
Calculator
0.2
0.4
0.6
1500
1301
1477
1639
1625
1381
1544
1699
1750
1463
1615
1763
1875
1548
1688
1828
2000
1633
1764
1897
2125
1720
1842
1967
2250
1808
1921
2040
2375
1897
2003
2115
2500
1987
2068
2191
Economizer
66
66
80
80
107
107
107
6.
Use the DOWN arrow key highlight the UNIT CONFIG-
URATIONS menu then press ENTER.
7.
Highlight UNIT CONFIGURATIONS then press ENTER.
8.
Highlight INDOOR FAN and then press ENTER.
9.
Refer to the job specifications to set the following, deter-
mining the values per the rpm Calculator label (see Fig. 9).
Use the UP and DOWN arrow keys and the BACK key to
set the values. Press ENTER after setting each value to
continue to the next selection.
IDF VENT SPD
IDF HEAT SPD
IDF LOW COOL SPD
IDF HIGH SPD
IDF FREE COOL SPD
For further details see the FC/GC Series Single Package Rooftop
Units with SystemVu Controller Controls, Start-up, Operation and
Troubleshooting manual.
ESP in. wg
0.8
1.0
1.2
1788
1925
2054
1843
1976
2101
1902
2031
2152
1962
2087
2206
2025
2146
2262
2090
2208
2320
2157
2271
2380
2227
2336
2298
66
66
66
66
80
80
80
80
107
107
107
7
A
1.4
1.6
1.8
2.0
2174
2289
2220
2332
2268
2378
2318
2372
66
66
80
80
107
107
Controls