Holding Register (0x03)
Register
40001
Operation Mode
40002
Control method (Circuit 1/2)
Target temp (Heating/Cooling)
40003
40004
Room Air Temp. Circuit 1
Shift value(Target) in auto mode
40005
Target temp (Heating/Cooling)
40006
40007
Room Air Temp. Circuit 2
Shift value(Target) in auto mode
40008
40009
DHW Target temp.
40010
Energy state input
Description
Circuit 1
Circuit 1
Circuit 2
Circuit 2
INSTALLER SETTING
Value explanation
0 : Cooling / 4 : Heating / 3 : Auto
0 : Water outlet temp. control
1 : Water inlet temp. control
2 : Room air control
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
0 : Not Use
1 : Forced off (equal to TB_SG1=close /
TB_SG2=open)
2 : Normal operation (equal to TB_SG1=open /
TB_SG2=open)
3 : On-recommendation (equal to
TB_SG1=open / TB_SG2=close)
4 : On-command (equal to TB_SG1=close /
TB_SG2=close)
5 : On-command step 2 (++ Energy
Consumption compared to Normal)
6 : On-recommendation Step 1 (+ Energy
Consumption compared to Normal)
7 : Energy Saving mode (- Energy Consumption
compared to Normal)
8 : Super Energy saving mode (-- Energy
Consumption compared to Normal)
163