Chengdu Ebyte Electronic Technology Co.,Ltd.
(6) DHCP: Set the way the device obtains IP: static (0), dynamic (1).
(7) Target IP: When the device works in client mode, the target IP or domain name of the device connection.
(8) Destination port: When the device is working in client mode, the destination port of the device
connection.
(9) DNS server: The device is in the client mode and resolves the domain name of the server.
(10) Module working mode: switch the working mode of the module. Server: The device is equivalent to a
server, waiting for the user's client to connect. The maximum number of connections is 4. Client: The device
actively connects to the target IP and port set by the user.
(11) Active upload: When this parameter is not 0, and the device is in the client mode, the discrete input status
of the device will be uploaded to the server when it is connected for the first time or the input changes, and the
analog input will be uploaded according to the configured time period.

4.3.4. Serial Port Parameters

Parameters for setting serial communication:
Default parameters:
Baud rate: 9600 (03);
Data bit: 8bit;
Stop bit: 1bit;
Check digit: NONE(00);
(1) Baud rate:
(2) Check Digit:

4.4 OLED display and parameter configuration

The display interface includes an information display page (AO input value display page) and a parameter
setting page (some parameters).
Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co.,Ltd.
Baud rate code value table
0x0000
1200
0x0001
2400
0x0002
4800
0x0003 (default)
9600
0x0004
19200
0x0005
38400
0x0006
57600
0x0007
115200
Check Digit
0x0000(default)
NONE
0x0001
ODD
0x0002
EVEN
ME31-XXXA0006_UserManual_EN
16