Haier GE AZ45E07EACW5 Technical Service Manual page 33

2019 zoneline air conditioner
Table of Contents

Advertisement

Fault
Code
Fault Meaning
Number
F10
Heat pump over-temperature
fault. The temperature of the
indoor coil is over 131°F.
F11
Inlet air temperature. Indoor air
thermistor warmer than 95°F.
F12
UI board disconnected/failed.
F13
Heater airflow fault: The main
board detects too low of indoor
fan speed.
F16
Make-Up Air module
communication fault.
F17
Outlet thermistor failure. Fault
clears when thermistor reads
value other than short circuit or
open circuit.
F18
Outlet temperature overheat.
The outgoing air is too hot. Fault
clears when air temperature
drops below threshold.
F19
Outlet temperature overheat.
The outgoing air is too hot.
F23
Make-up Air Module Fault
F24
Make-up Air Module Vent Door
Fault
F25
Abnormal Defrost Fault (heat
pump models only). Set when
five consecutive defrost cycles
failed to warm outdoor coil above
68°F.
F26
Air Conditioning Lockout Fault
(heat pump models only).
Sets when outdoor ambient
temperature drops below 35°F.
Effect on Operation
While Fault is ACTIVE
The outdoor fan motor is
shut down until the coil
temperature recovers.
Shut off compressor and
resistance heat operation
until inlet thermistor
temperature drops below
85°F.
No effect.
No resistance heat or heat
pump available.
No communication
between Zoneline and
Maku-Up air module.
No resistance heating
available.
No resistance heating
available.
No resistance heating
available.
Shuts Down MUAM,
including MUAM
compressor
This is set if the vent door
state change validation
fails.
Locks out heat pump,
locks out defrost.
Locks out compressor
cooling operation.
– 33 –
Fault Reset Time
Fault clears
once indoor coil
temperature drops
below 122°F.
Fault clears once air
temperature drops
below 85°F.
Fault clears after X
minutes.
No effect
Will self-clear after 4.5
days.
Will self-clear after
Outdoor Ambient
temperature rises
above 40°F.