12.1 Modes of operation:
Three Phase Current and Voltage
Positioning Coils
Care should be taken when positioning coils during the set
up of the logger to ensure they are well spaced, don't
overlap or are placed too closely to neighbouring
conductors. Poor positioning of coils can prevent the logger
configuring automatically.
The coil around the blue conductor is too close to the yellow
conductor. Ensure that coils are not positioned too closely to
neighbouring conductors.
If the conductors are close together, coils can be angled
around conductors.
20
When separating coils, move them holding the grey cable.
Holding the green part of the coil may affect the set up.
Ensure coils are not positioned next to secondary conductors
from the other phases.
Once the logger has automatically configured and logging
has been started, the position of the coils is no longer
important and as long as they are left around the conductors
they were configured to the logger will record correctly.
21