■ RAP Valve Kit (Refrigerant Accumulation Protector Valve Kit) (CZ-P160RVK2)
When installing a H1 type indoor unit, you must also install the RAP Valve Kit (CZ-P160RVK2).
● Necessary number of connecting RAP valve kit per one indoor unit.
Indoor unit type
Necessary number
● Secure the RAP valve kit using suspension bolts, etc. within 30 m from the indoor unit.
● Do not place the RAP valve kit directly on the ceiling.
Supplied strainer assembly
Indoor Unit Side
Liquid tube ø6.35
6P connector (5 m)
Note: This figure shows the valve body with the suspension hook and strainer assemblies installed.
140
224/280
2 kits
1 kit
in parallel
Gas tube ø15.88
Suspension hook
CAUTION
Service cover
3
5
4
319
159.5
Valve body
6
2
1045
Gas tube ø15.88
Supplied strainer assembly
Outdoor Unit Side
Liquid tube ø6.35
3
7
2
6
2
11
Unit: mm