8. Locations To Avoid

(See Figures 7-A, 7-B, & 7-C for recommended locations)
• In the garage. Products of combustion are present when you start your automobile.
• Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence
feature and should not be installed within 6 ft of cooking appliances.
• Do not install within 6 ft of heating appliances.
• Less than 4" (10cm) from the peak of an "A" frame type ceiling.
• In an area where the temperature may fall below 40ºF or rise above 100ºF, such as garages and unfinished
attics.
• In dusty areas. Dust particles may cause nuisance alarms or a failure to alarm.
• In very humid areas (above 95% RH, non-condensing) as moisture or steam can cause nuisance alarms.
• In insect-infested areas.
• Smoke alarms should not be installed within 3 ft (.9m) of the door to a bathroom containing a tub or show-
er, forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high
air flow areas.
• Near lights. Electronic "noise" generated by the lights may cause nuisance alarms.
• Do not install near vents, flues, or chimneys.
• Do not install near fans, doors, windows or areas directly exposed to the weather.