Kidde HD135F - Heat Alarm Manual

Kidde HD135F - Heat Alarm Manual

Also See for HD135F:

Advertisement

Kidde HD135F - Heat Alarm Manual

Introduction

AC Wire-in Single and/or Multiple Station (up to 24 Devices) Heat Alarm with 9 Volt Battery Back Up, 135ºF fixed temperature.
Thank you for purchasing this heat alarm. It is an important part of your family's home safety plan. You can trust this product to provide the highest quality safety protection. We know you expect nothing less when the lives of your family are at stake. Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms. Connection of Kidde products to a non-specified manufacturer's interconnect system, or connection with non-specified equipment from another manufacturer into an existing Kidde system could result in nuisance alarming, failure to alarm, or damage to one or all of the devices in the interconnect system. Refer to the User's Guide supplied with each Kidde product for interconnect compatible models, brands, and devices. Refer to the wiring instructions in LOCATIONS TO AVOID section for NFPA initiating device limits

BATTERY DOOR WILL NOT CLOSE UNLESS A BATTERY IS PRESENT. REMOVAL OF THE HEAT ALARM BATTERY AND DISCONNECTING OR LOSS OF AC POWER WILL RENDER THE HEAT ALARM INOPERATIVE.
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm (maximum 80mA for originating unit with 24 devices interconnected).

READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE.

THIS HEAT ALARM IS NOT DESIGNED TO PROTECT LIFE SAFETY AGAINST FIRE AND SMOKE.
SEE LIMITATIONS OF ALARMS SECTION FOR DETAILS.
Do not try to repair this heat alarm yourself. Refer to the instructions in for service.

SPECIFICATIONS

Model Number HD135˚F
AC 120 VAC, 60HZ, 80 mA max, 9 V battery backup, Multiple station (up to 24), compatible with Kidde/Lifesaver smoke alarms.
U.L. Temperature rating 135ºF Fixed temperature only
U.L. Maximum ambient temperature at ceiling 100ºF
U.L. Recommended coverage 2500 Square Feet (Note "A")
U.L. recommended spacing 50 Feet
Maximum distance from wall 25 Feet (Note"B")
Note A: Maximum coverage established by U.L. is based on providing equal response time as sprinkler devices spaced at 10-Ft intervals (100 Sq/Ft) on a smooth ceiling approximately 15 feet high. Higher ceilings may adversely affect response time and earlier response time may be obtained by reducing the spacing between alarms.
Note B: Maximum distance is from any wall or ceiling projection extending down more than 12 inches.

  • The most favorable mounting locationfor a heat alarm is on the ceiling in the center of the room. At this location the alarm is closest to all areas of the room (see figure 3).
    Recommended Location - Part 1
    EXCEPTION: When the mounting surface might become considerably warmer or cooler than the room, such as a poorly insulated ceiling, below an unfinished attic, or an exterior wall. In these cases the alarm should be mounted on an inside wall.
  • If the alarm cannot be located in the center of the room, an off-center location can be used on the ceiling. When off center mounting an alarm on the ceiling, locate it at a minimum of 4" (10 cm) from the side wall (see figure 3).
  • If a ceiling mounting location is not feasible the next logical location for mounting heat alarms is on the side wall. When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a minimum of 4" (10 cm) and a maximum of 12" (30.5 cm) below the ceiling (see figure 1).
    Recommended Location - Part 2
  • Install Heat Alarms on sloped, peaked or cathedral ceilings at or within 3 ft (0.9m) of the highest point (measured horizontally). NFPA 72 states: "Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4m) horizontally shall be located on the high side of the room." NFPA 72 states: "A row of alarms shall be spaced and located within 3 ft (0.9m) of the peak of the ceiling measured horizontally" (see figure 3).
  • In rooms with open joists or beams, all ceiling mounted alarms shall be located on the bottom of such beams (see figure 2).
    Recommended Location - Part 3
  • Alarms installed on an open-joisted ceiling shall have their smooth ceiling spacing reduced to no more than half of the listed spacing when measured at right angles to the solid joist (See figure 2).

MOBILE HOME INSTALLATION

Modern mobile homes have been designed and built to be energy efficient. Install heat alarms as recommended above (refer to RECOMMENDED LOCATIONS and FIGURE 1).
In older mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the heat from reaching an alarm mounted on the ceiling. In such units, install the heat alarm on an inside wall with the top edge of the alarm at a minimum of 4" (10 cm) and a maximum of 12" (30.5 cm) below the ceiling (see figure 1).
If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall.

TEST YOUR HEAT ALARM OPERATION AFTER RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.

LOCATIONS TO AVOID

  • In front of forced air supply ducts used for heating and air conditioning, nearceiling fans, or other high air flow areas.
  • In an area where the temperature may fall below -20ºF or rise above 100ºF.
  • Near fluorescent lights – electronic "noise" may cause nuisance alarms.
  • Heat alarms are not to be used with detector guards unless the combination(alarm and guard) have been evaluated and found suitable for that purpose.

INSTALLATION INSTRUCTIONS

WIRING REQUIREMENTS

  • This smoke alarm should be installed on a U.L. listed or recognized junction box. All connections should be made by a qualified electrician and all wiring used shall be in accordance with articles 210 and 300.3(B) of the U.S. National Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdiction in your area. The multiple station interconnect wiring to the alarms must be run in the same raceway or cable as the AC power wiring. In addition, the resistance of the interconnect wiring shall be a maximum of 10 ohms.
  • The appropriate power source is 120 Volt AC Single Phase supplied from a non-switchable circuit which is not protected by a ground fault interrupter.

  • This alarm cannot be operated from power derived from a square wave or modified square wave inverter. These type of inverters are sometimes used to supply power to the structure in off grid installations, such as solar or wind derived power sources. These power sources produce high peak voltages that will damage the alarm.

WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS


TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.

  • For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING. Leave the red wire insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box.
  • When alarms are interconnected, all interconnected units must be powered from a single circuit.
  • A maximum of 24 Kidde/Lifesaver devices may be interconnected in a multiple station arrangement. The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon monoxide, etc.). With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.
  • When mixing models which have battery backup (1275, 1276, 1285, 1296, i12040, i12040A, i12060, i12060A, i12080, i12080A, i4618, i4618A, PE120, P12040, PI2000, PI2010, KN-COPE-i, KN-SM-FM-i, KN-COSM-IB, HD135F, KN-COB-IC, KN-COP-IC) with models without battery backup, (1235, i12020, i12020A, KN-COSM-I,120X, SM120X, CO120X, SL177i) be advised that the models without battery backup will not respond during an AC power failure.
  • The maximum wire run distance between the first and last unit in an interconnected system is 1000 feet.
  • Figure 4 illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to operate, or a shock hazard.
  • Make certain alarms are wired to a continuous (non-switched) power line.
    NOTE: Use standard UL listed household wire (as required by local codes) available at all electrical supply stores and most hardware stores.

Interconnect Wiring Diagram
FIGURE 4 INTERCONNECT WIRING DIAGRAM

WIRES ON ALARM HARNESS CONNECTED TO
Black Hot Side of AC Line
White Neutral Side of AC Line
Red Interconnect Lines (Red Wires) of Other Units in the Multiple Station Set up

BATTERY INSTALLATION

See MAINTENANCE for battery installation.

IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING (SEE FIGURE 9).

MOUNTING INSTRUCTIONS


THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!

  1. Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm in the direction indicated by the "OFF" arrow on the alarm cover.
  2. After selecting the proper smoke alarm location as described in RECOMMENDED LOCATIONS OF ALARMS Section and wiring the AC QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to the electrical box (see figure 5).
  3. Use a screwdriver to punch out only the pair of holes in the trim ring that match your type of electrical box or plaster ring. Mount the trim ring to the electrical box, using the appropriate holes. NOTE: Use the circle, square and octagon markings near each mounting hole in the trim ring to help you select the correct mounting holes (see figure 5).
    Select Correct Mounting holes On Trim Ring
  4. Pull the AC QUICK CONNECTOR through the center hole in the trim ring and mount the ring, making sure that the mounting screws are positioned in the small ends of the keyholes before tightening the screws (see figure 5).
  5. Plug the AC QUICK CONNECTOR into the back of the alarm (see figure 6), making sure that the locks on the connector snap into place. Then push the excess wire back into the electrical box through the hole in the center of the trim ring.

    (To remove AC connector, squeeze locking arms and pull.)
  6. If you have finished all the WIRING, BATTERY INSTALLATION AND TRIM RING MOUNTING STEPS, you can install the alarm on the trim ring. Alignment marks are provided on the side of the alarm and on the trim ring (see figure 7).
    Mounting
  7. Install the alarm on the trim ring with the indicating marks aligned and rotate the alarm in the direction of the "ON" arrow on the cover until the alarm snaps in place (see figure 7).
  8. Turn on the AC power. The green AC Power On Indicator should be lit when the alarm is operating from AC power.

TAMPER RESIST LOCKING PIN: To make your heat alarm tamper resistant, a locking pin has been provided with your alarm. Using this pin will help deter children and others from removing the alarm from trim ring. To use the pin, insert it into the hole in the side of the alarm after the alarm has been installed on the trim ring (see figure 8).

NOTE: The tamper resist pin will have to be removed in order to change the batteries. Use long nose pliers to pull the pin out of the hole. It is now possible to remove the alarm from the trim ring.
After installation, TEST your alarm by pressing and holding the test button for several seconds. You can also use a hand held hair dryer to test your heat alarm. Complete details on this procedure are outlined in section OPERATION AND TESTING.

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke alarm installed in each separate sleeping area (in the vicinity of - but outside of the bedroom) and heat or smoke alarms in the living rooms, dining rooms, kitchens, hallways, attics, furnace rooms, closets, utility storage rooms, basements, and attached garages.

OPERATION AND TESTING

OPERATION: The heat alarm is operating once AC power is applied, fresh batteries are installed and testing is complete. When the heat alarm senses temperatures above 135ºF (plus or minus a few degrees), the horn will sound a loud (85 db) pulsating alarm until the temperature drops below 135ºF.

LED INDICATORS: This heat alarm is equipped with red and green LED indicators. The red LED is located under the test button and has two modes of operation.
Standby Condition:
The red LED will flash every 30-40 seconds to indicate that the smoke alarm is operating properly.
Alarm Condition:
When the unit detects heat and goes into alarm, the red LED will flash rapidly (one flash per second). The rapid flashing LED and pulsating alarm will continue until the temperature drops below 135 ºF.
WHEN UNITS ARE INTERCONNECTED, only the red LED of the originating alarm or alarm being tested will flash rapidly. All other units in the interconnect system will sound an alarm but their red LED's will NOT flash rapidly.
The green LED is located under the other button.
Standby Condition:
The green LED will be steady on, indicating the presence of AC power.

TESTING: Test by pushing the test button on the cover and hold it down for a minimum of 5 seconds. This will sound the alarm if all the electronic circuitry, horn, and battery are working. THE TEST SWITCH MAY NOT CAUSE A TEST SIGNAL IF THE AMBIENT TEMPERATURE IS BELOW 32ºF, IN THIS CASE TEST THE UNIT BY BLOWING HOT AIR AT THE ALARM SENSING ELEMENT WITH A HAIR DRYER HELD ABOUT 1 FOOT FROM THE UNIT.
If no alarm sounds, check the fuse or circuit breaker supplying power to the alarm circuit, if the alarm still does not sound the unit may have defective batteries or other failure.
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION.
Erratic or low sound coming from your alarm may indicate a defective alarm, and it should be returned for service.

FALSE ALARMS

To avoid false alarms, DO NOT USE WHERE ROOM TEMPERATURES WILL EXCEED 100º F.
Heat alarms respond only to heat. They do not detect smoke. If the unit does alarm, check for fires first. If a fire is discovered, get out of the house and call the fire department. If no fire is present check to see if one of the reasons listed in section LOCATIONS TO AVOID may have caused the alarm.

MAINTENANCE

ALARM REMOVAL

IF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCKING PIN IN INSTALLATION INSTRUCTIONS SECTION FOR PIN REMOVAL INSTRUCTIONS.
To replace the battery, remove the alarm from the trim ring by rotating the alarm in the direction of the "OFF" arrow on the cover (see figure 7). To disconnect the AC power harness, squeeze the locking arms on the sides of the Quick Connector while pulling the connector away from the bottom of the alarm (see figure 6).

BATTERY INSTALLATION AND REMOVAL

To replace or install the batteries, you must first remove the alarm from the trim ring by following the ALARM REMOVAL instructions at the beginning of this section. After alarm has been removed, you can open the battery door and install or replace the battery. Battery installation instructions are provided on the inside of the battery door.
When installing the battery, press the battery reminder finger down into the battery compartment and install the battery (see figure 9).


IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING.
This smoke alarm uses a 9V carbon backup battery (alkaline and lithium batteries may also be used). A fresh battery should last for one year under normal operating conditions.
This alarm has a low/missing battery monitor circuit which will cause the alarm to "chirp" approximately every 30-40 seconds for a minimum of seven (7) days when the battery gets low. Replace the battery when this condition occurs.
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM REPLACEMENT.

Carbon-zinc type EVEREADY 216 OR 1222;
GOLD PEAK 1604P OR 1604S
Alkaline type ENERGIZER 522;
DURACELL MN1604, MX1604; GOLD PEAK 1604A;
PANASONIC 6AM6, 6AM-6, 6AM-6PI, 6AM6X, and 6LR61(GA)
Lithium type ULTRALIFE U9VL-J

NOTE: WEEKLY TESTING IS REQUIRED!

BE SURE TO FOLLOW BATTERY INSTALLATION INSTRUCTIONS PRINTED ON THE INSIDE OF THE BATTERY DOOR AND USE ONLY THE BATTERIES SPECIFIED. USE OF DIFFERENT BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.

CLEANING YOUR ALARM

YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR
To clean your alarm, remove it from the mounting bracket as outlined in the beginning of this section. You can clean the interior of your alarm (sensing chamber) by using compressed air or a vacuum cleaner hose and blowing or vacuuming through the openings around the temperature sensor located on the top of the alarm. The outside of the alarm can be wiped with a damp cloth. After cleaning, reinstall your alarm and test your alarm by using the test button. If cleaning does not restore the alarm to normal operation the alarm should be replaced.
After cleaning, reinstall your alarm. Test your alarm by using the test button and check that the green LED is on.

LIMITATIONS OF HEAT ALARMS


PLEASE READ CAREFULLY AND THOROUGHLY

  • HEAT ALARMS ARE NOT DESIGNED TO PROTECT LIFE SAFETY AGAINST FIRE AND SMOKE. IN MOST FIRES, HAZARDOUS LEVELS OF TOXIC GASES, SMOKE AND HEAT CAN BUILD UP BEFORE A HEAT ALARM WILL OPERATE. IN CASES WHERE LIFE SAFETY IS AN ISSUE, HEAT ALARMS SHOULD ONLY BE USED TO PROVIDE AN ADDED SOURCE OF INFORMA- TION AND AS A SUPPLEMENT TO THE SMOKE ALARM INSTALLATION. HEAT ALARMS DO NOT ALWAYS DETECT FIRES, THE FIRE MAY BE A SLOW SMOLDERING (SMOKE PRODUCING) LOW HEAT PRODUCING TYPE, THE FIRE MAY BE IN A DIFFERENT ROOM THAN THE ALARM, OR THE HEAT FROM THE FIRE MAY BYPASS THE ALARM. THIS ALARM WILL NOT DETECT SMOKE, GASES OR FLAMES.
  • HOME FIRES DEVELOP IN DIFFERENT WAYS AND ARE OFTEN UNPREDICTABLE. NO ONE TYPE OF ALARM (HEAT, PHOTOELECTRIC OR IONIZATION) IS ALWAYS BEST, AND A GIVEN ALARM MAY NOT ALWAYS PROVIDE WARNING OF A FIRE. ALSO ALARMS DO HAVE LIMITATIONS. FOR A BATTERY POWERED ALARM THE BATTERY MUST BE OF THE SPECIFIED TYPE, IN GOOD CONDI- TION AND INSTALLED PROPERLY. AC POWERED ALARMS WILL NOT OPERATE IF AC POWER HAS BEEN CUT OFF SUCH AS BY AN ELECTRICAL FIRE OR AN OPEN FUSE. ALARMS MUST BE TESTED REGULARLY TO MAKE SURE THE BAT- TERIES AND THE ALARM CIRCUITS ARE IN GOOD OPERATING CONDITION.
  • HEAT ALARMS CANNOT PROVIDE AN ALARM IF HEAT DOES NOT REACH THE ALARM. THEREFORE, HEAT ALARMS MAY NOT SENSE FIRES STARTING IN CHIMNEYS, WALLS, ON ROOFS, ON THE OTHER SIDE OF A CLOSED DOOR OR ON A DIFFERENT FLOOR. IF THE ALARM IS LOCATED OUTSIDE THE BEDROOM OR ON A DIFFERENT FLOOR, IT MAY NOT WAKE UP A SOUND SLEEPER. THE USE OF ALCOHOL OR DRUGS MAY ALSO IMPAIR ONES ABILITY TO HEAR THE ALARM. FOR MAXIMUM PROTECTION HEAT ALARMS SHOULD ONLY BE USED AS A SUPPLEMENT TO SMOKE ALARMS. SMOKE ALARMS SHOULD BE INSTALLED IN EACH SLEEPING AREA ON EVERY LEVEL OF A HOME AND BE INTERCONNECTE WITH EACH OTHER AND THE HEAT ALARMS.
  • ALTHOUGH HEAT ALARMS WHEN COMBINED WITH SMOKE ALARMS, CAN HELP SAVE LIVES BY PROVIDING AN EARLY WARNING OF A FIRE, THEY ARE NOT A SUBSTITUTE FOR AN INSURANCE POLICY. HOME OWNERS AND RENTERS SHOULD HAVE ADEQUATE INSURANCE TO PROTECT THEIR LIVES AND PROPERTY.

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Kidde HD135F - Heat Alarm Manual

Advertisement

Need Assistance?

Do you have a question about the HD135F that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents