Emerson Copeland OME-4MTL-12X Application Manuallines page 63

Refrigeration units for co2 applications
Table of Contents

Advertisement

Name on
Code
Description
Visograph
High pressure on
PreHP Rec
PreHP Rec
CO
alarm
High pressure on
HP REC
HP REC
CO
alarm
Low pressure on
LP REC
LP REC
CO
alarm
OA-
XEV20D off-line
OA-XEV20D
XEV20D
alarm
Table 25: Alarm code overview
58
Cause
receiver pre-
GC28 > AIC98 (AIC99) > GC29
2
receiver
AIC98 (AIC99) > GC28
2
receiver
AIC98 (AIC99) < GC31
2
The XEV20D is used and loses
communication
Gas cooler alarms
Action
(Priority on probe failure
alarms)
The % of the valve updates
every second in order to reach
the correct percentage.
If the receiver pressure value
is between the values GC29
and GC28 – 1 (bar), the % of
valve opening is as follows:
(Priority on probe failure
alarms)
The HPV will close (0 %).
The BGV will open to a user-
defined % set by parameter
GC37.
The HPV will have a minimum
opening to a user-defined %
set by GC36.
If the PID % is greater than
GC36, then the PID % will be
the valve % output.
The BGV will close.
Only signalling
Reset
Automatically as soon as the HP REC
is active or as soon as AIC98 (AIC99) <
GC29 – GC30
Automatically as soon as AIC98
(AIC99) < GC28 – GC30
Automatically as soon as AIC98
(AIC99) > GC31 + GC32
The communication is recovered
automatically
AGL_Unit_OME_4MTL_EN_Rev01