Name on
Code
Description
Visograph
Probe failure
P1
P1
alarm
Probe failure
P2
P2
alarm
Probe failure
P3
P3
alarm
Probe failure
P4
P4
alarm
Probe failure
P5
P5
alarm
Probe failure
P6
P6
alarm
Probe failure
P7
P7
alarm
Probe failure
P8
P8
alarm
Probe failure
P9
P9
alarm
Probe failure
P10
P10
alarm
BURST
ALBST
Burst disc alarm
Phase failure
PHASE
ALPHS
alarm
EXT[i]
EXT[i]
External alarm (i)
Receiver level
LIQ LVL
LIQ LVL
alarm
REC
Receiver high
REC FLOAT
FLOAT
pressure alarm
Alarm to change
OIL DIFF
OIL DIFF HI
oil separator
HI
switching element
AGL_Unit_OME_4MTL_EN_Rev01
Generic alarms
Cause
Probe 1 failure
Probe 2 failure
Probe 3 failure
Probe 4 failure
Probe 5 failure
Probe 6 failure
Probe 7 failure
Probe 8 failure
Probe 9 failure
Probe 10 failure
DIC(i) = 72 activation
DIC(i) = 73 activation
DIC(i) = 74 (or 75 - 76 - 77)
activation
80 % < Liquid level input < 15 %
for 45 min
Contact closure from receiver
rupture disc
Contact closure from change oil
separator input > 1 minute
Action
Reset
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Automatically as soon as the probe
Only signalling
restarts working
Only signalling
DIC(i) = 72 deactivation
Only signalling
DIC(i) = 73 deactivation
Only signalling
DIC(i) = 74 (or 75 - 76 - 77) deactivation
Automatically when
Only signalling
15 % < Liquid level < 89 %
Only signalling
Must be cleared manually on site
Only signalling
Automatically when DI is false