2.8.3

Liquid receiver

The liquid receiver (24.9 litres for the whole range of units) is installed below the gas cooler. It is
equipped with a shut-off valve on the outlet and a safety group (2 pressure relief valves 90 bar,
connected to a switch-over valve).
There are 2 sight glasses in the shell of the liquid receiver to check the refrigerant level.
2.8.4

Fan

The gas cooler of the Copeland CO
Fan
Unit
OME-4MTL-05X
FN071-6IQ.BD.V7P3
OME-4MTL-07X
OME-4MTL-09X
FN071-ZIQ.DG.V7P3
OME-4MTL-12X
Table 5: Fan specifications
Technical data
Supply frequency
Supply voltage
Min to max ambient temperature
ErP 2015
IP class
Fan motor type
Fan blades
Table 6: Fan technical data

Figure 10: Fan design

2.8.5

Gas cooler regulation valve (HPV)

The high-pressure regulation valve is installed between the gas cooler and the liquid receiver. It
regulates the high pressure for optimum COP in transcritical operation.
The driver for the stepper motor valve is installed in the electrical cabinet.
The driver for the HPV is an XEV20D. It gets a signal from the unit controller – see section 2.9 "CO2
Unit control – General".
10
refrigeration unit is equipped with an EC fan.
2
Description
50/60 Hz
200-277 V
-35 to +60 °C
Plastic
Power
Maximal
input
current
(W)
(A)
280
1.4 - 1.0
660
3.4 - 2.4
Yes
IP54
EC
AGL_Unit_OME_4MTL_EN_Rev01
Air flow
(m³/h)
7100
11950