Siemens SIMATIC HMI TP700 Comfort Operating Instructions Manual page 16

Hide thumbs Also See for SIMATIC HMI TP700 Comfort:
Table of Contents

Advertisement

Mounting and connecting the HMI device
3.1 Preparing for installation
Mounting position
Select one of the approved mounting positions for your device. The approved mounting
positions are described in the following sections.
Mounting in horizontal format
Ambient temperature when mounted in horizontal format:
● Vertical mounting (0° inclined): Maximum +60 °C
● Inclined mounting (inclined up to 35°): Maximum +50 °C
Mounting in vertical format
Ambient temperature when mounted in vertical format:
● Vertical mounting (0° inclined): Maximum +50 °C
● Inclined mounting (inclined up to 35°): Maximum +45 °C
See also
Operating Conditions (Page 27)