6. Specifications
* Derate capacity to 80% of capacity when the output voltage is adjusted to 100VAC, 200VAC or 208VAC.
** Product specifications are subject to change without further notice.
MODEL
CAPACITY*
INPUT
Low Line
Transfer
Low
Voltage
Line
Range
Come
back
High Line
Transfer
High
Line
Come
back
Frequency Range
Phase
Power Factor
THDi
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized
Range)
Frequency Range
Current Crest Ratio
Harmonic Distortion
AC Mode to
Transfer
Batt. Mode
Time
Inverter to
Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
ECO Mode
Battery Mode
BATTERY
Battery Type
Numbers
Recharge Time
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H
(in.)
Net Weight (lbs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
DC1000RTX1
DC1500RTX1
1000VA/1000W
1500VA/1500W
160VAC/140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/55VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175VAC/155VAC/135VAC/125VAC ± 5 % or 87VAC/77VAC/67VAC/62VAC ± 5 %
≧89% @ full charged battery
≧88%
12V/7AH
3
3 hours recover to 95% capacity for internal battery@ 2A charging current
100/110/115/120 /127 VAC models: default 2A, max. 8A
adjustable 200/208/220/230/240 VAC models: default 2A,
max. 12A adjustable
41.0 VDC ± 1%
41.0 VDC ± 1%
16.5 x 17.25 x 3.5
32
Power management from SNMP manager and web browser
DC2000RTX1
2000VA/2000W
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
≧ 0.99 @ full load
≦ 5% @ 205-245VAC or 100~130VAC
THDU < 1.6% @ input and full linear load condition
200/208/220/230/240VAC or 100/110/115/120/127 VAC
± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
3:1
≦ 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Zero
< 4 ms
Pure Sinewave
≧91% @ full charged battery
≧96% @ full charged battery
12V/9AH
12V/9AH
3
4
54.7 VDC ± 1%
20.5 x 17.25 x 3.5
35
43
20-95 % RH @ 0- 40°C (non-condensing)
Less than 50dBA @ 1 Meter (With fan speed control)
Supports Windows® 7/8/10/11, Linux, Unix and MAC
30
DC3000RTX1
DC3000RTX1HV
3000VA / 3000W
3000VA / 3000W
≧90%
12V/9AH
6
Default: 2A, Max: 8A adjustable
82.1 VDC ±1%
24.8 x 17.25 x 3.5
61
61