Wind-free 4way cassette for america (r410a, hp)
Hide thumbs Also See for AC009BNNDCH/AA:

Advertisement

Installation
Outdoor Units
NOTE
• RLA is based on AHRI 210/240 cooling standard
condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 °C /
67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)]
• Voltage tole rance is ± 10 %.
• Maximum allowable volta ge between phases is 2 %.
• Symbols
– RLA: Rated Load Ampere (A)
– MOC: Maximum Operating Current (A)
– MCA: Minimum Circu it Ampere (A)
– MOP: Maximum Overcurrent Protective Device (A)
• Voltage range
– Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
• Maximum allowable voltage va riation between phases
is 2%.
• Wire size & typ e must comply with the applicable local
and national code.
– Wire size: Based on the value of MCA.
– Wire type:
1-phase: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more
Silence mode controller wiring diagram with
External controller
• AC009/012/018BXADCH
2Pin
4Pin
(RED)
(RED)
External controller
• AC024/030/036/042/048BXADCH
4Pin(RED)
2Pin (RED)
Non-voltage contact
Non-voltage
contact
External controller

Advertisement