Installation
Indoor Units
Power supply
208 to 230V, 60 Hz
Communication cable
0.0012 inch² ↑(0.75mm²↑), 2 wires
AC power: M4 screw
0.39(9.8)
0.50(12.6)
Tightening torque lbf·ft (kgf • cm)
M3.5
M4
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
• Select the power cable in accordance with relevant
local and national.
• Wire size must comply with local and national code.
• You should connect the power cable into the power
cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 10%
of supply rating among whole indoor units.
If the power is unbalanced greatly, it may shorten
the life of the condenser. If the unbalanced power
is exceeded by more than 10% of supply rating,
the indoor unit will protect itself by stopping and
displaying an error code.
Connect the power cable to the auxiliary circuit
breaker. An all pole disconnection from the power
supply must be incorporated in the fixed wiring
(≥0.12inch (3mm)).
Indoor power supply
Max/Min(V)
Indoor power cable
0.0012 inch² ↑
±10%
(0.75mm²↑), 3 wires
Unit: inch(mm)
Unit:inch(mm)
Communication: M3.5 screw
0.30(7.5) 0.35(9.0)
0.58 to 0.87 (8.0 to 12.0)
0.87 to 1.30 (12.0 to 18.0)
• You must keep the cable in a protection tube.
• Maximum length of power cables are decided within
10% of power drop. If it exceeds, you must consider
another power supplying method.
• The circuit breaker (MCCB, ELB) should be considered
more capacity if many indoor units are connected from
one breaker.
• Use round pressure terminal for connections to the
power terminal block.
• For wiring, use the designated power cable and
connect it firmly, then secure to prevent outside
pressure being exerted on the terminal board.
• Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
• Over-tightening the terminal screws may break them.