Installation
Indoor Units
Power supply
208 to 230V, 60 Hz
Communication cable
0.0012 inch² ↑(0.75mm²↑), 2 wires
AC power: M4 screw
0.39(9.8)
0.50(12.6)
Tightening torque lbf·ft (kgf • cm)
M3.5
M4
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
• Select the power cable in accordance with relevant
local and national.
• Wire size must comply with local and national code.
• You should connect the power cable into the power
cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 10%
of supply rating among whole indoor units.
•
If the power is unbalanced greatly, it may shorten
the life of the condenser. If the unbalanced power
is exceeded by more than 10% of supply rating,
the indoor unit will protect itself by stopping and
displaying an error code.
•
Connect the power cable to the auxiliary circuit
breaker. An all pole disconnection from the power
supply must be incorporated in the fixed wiring
(≥0.12inch (3mm)).
Indoor power supply
Max/Min(V)
Indoor power cable
0.0012 inch² ↑
±10%
(0.75mm²↑), 3 wires
Unit: inch(mm)
Unit:inch(mm)
Communication: M3.5 screw
0.30(7.5) 0.35(9.0)
0.58 to 0.87 (8.0 to 12.0)
0.87 to 1.30 (12.0 to 18.0)
• You must keep the cable in a protection tube.
• Maximum length of power cables are decided within
10% of power drop. If it exceeds, you must consider
another power supplying method.
• The circuit breaker (MCCB, ELB) should be considered
more capacity if many indoor units are connected from
one breaker.
• Use round pressure terminal for connections to the
power terminal block.
• For wiring, use the designated power cable and
connect it firmly, then secure to prevent outside
pressure being exerted on the terminal board.
• Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
• Over-tightening the terminal screws may break them.