Fujitsu AO G24LBCB Series Service Instruction page 43

Floor ceiling type / duct type / cassette type, inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

Trouble shooting 14
rouble shooting 14
INDOOR UNIT Error Method:
INDOOR UNIT Error Method:
Indoor Heat Ex. middle temp.
sensor Error
Detective Actuators:
Indoor Unit Controller PCB
Heat Exchanger (MID) Thermistor
Forecast of Cause : 1. Connector failure connection
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
CN32
B
BLACK
2
BLACK
1
CN8
BLACK
2
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indicate or Display:
Error code : 42
Detective details:
Indoor unit thermistor is open or short is detected always.
0
5
10
176
134
103
40
45
50
25.6
20.8
17.1
H/E Thermistor
Room Temp. Thermistor
2. Thermistor failure 3. Controller PCB failure
15
20
25
80.3
62.9
49.7
02-15
Outdoor unit : No indication
30
35
39.6
31.7