Download Print this page

Honeywell FIRE-LITE ALARMS SD365CO Installation And Maintenance Instructions page 3

Multi-criteria co and smoke sensor

Advertisement

a triangle on the sensor cover. (See Figure 3.) Use the applicator straw
included with the CO agent to more efficiently direct the CO into the
detection cell during testing.
The detector will go into alarm if gas entry is successful. It may take up
to 1 minute for the device to alarm. Once the detector is in alarm allow
5 minutes for the CO to clear and exit the detector.
The detector will automatically enable the signal processing after 10 min-
utes.
Testing the detector will activate the alarm relay and send a signal to
the panel.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1.
Remove the sensor to be cleaned from the system.
2.
Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. (See Figure 4.)
3.
Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4.
Remove the chamber cover/screen assembly by pulling it straight out.
5.
Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6.
Reinstall the chamber cover/screen assembly by aligning the arrows on
the top with the two round-top posts on the sensing chamber, and gently
pressing it until it fits securely.
7.
Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place. NOTE: Make sure that the thermistors
do not become bent under the cover.
8.
Reinstall the detector.
9.
Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
ABOUT CARBON MONOXIDE DETECTORS
CAUTION: This carbon monoxide detector is designed for indoor use only.
Do not expose to rain or moisture. Do not knock or drop the detector. The
detector will not protect against the risk of carbon monoxide poisoning if
not properly wired. The detector will only indicate the presence of carbon
monoxide gas at the sensor. Carbon monoxide gas may be present in other
areas.
This carbon monoxide detector is NOT:
• Designed to detect any gas other than carbon monoxide
• To be seen as a substitute for the proper servicing of fuel-burning appli-
ances or the sweeping of chimneys.
• To be used on an intermittent basis, or as a portable alarm for the spill-
age of combustion products from fuel-burning appliances or chimneys.
Carbon monoxide gas is a highly poisonous gas which is released when fuels
are burnt. It is invisible, has no smell and is therefore impossible to detect
with the human senses. Under normal conditions in a room where fuel burn-
ing appliances are well maintained and correctly ventilated, the amount of
carbon monoxide released into the room by appliances should not be danger-
ous.
SYMPTOMS OF CARBON MONOXIDE POISONING
Carbon monoxide bonds to the hemoglobin in the blood and reduces the
amount of oxygen being circulated in the body. The following symptoms
are examples taken from NFPA 720. They represent approximate values for
healthy adults:
CAUTION
Concentration (ppm CO)
200
400
800
Many causes of reported carbon monoxide poisoning indicate that while vic-
tims are aware that they are not well, they become so disoriented that they
are unable to save themselves by either exiting the building or calling for
assistance.
Also young children and pets may be the first to be affected.
Per UL standard 2075, the SD365CO has been tested to the sensitivity limits
defined in UL standard 2034.
ALARM THRESHOLDS ARE AS FOLLOWS:
Parts Per Million
70 ±5ppm
150 ±5ppm
400 ±10ppm
What to do if the carbon monoxide detector goes into alarm:
Immediately move to a spot where fresh air is available, preferably out-
doors.
IMPORTANT: This detector should be tested and maintained regularly fol-
lowing National Fire Protection Association (NFPA) 720 requirements.
CO SENSOR LIFETIME
The CO cell has an expected lifetime of approximately ten years. The detector
is programmed to signal the approach of end of this lifetime to the control
panel. The CO cell is not a field replaceable component. The smoke sensor
will continue to operate using other sensing elements (photoelectric, heat and
infrared) even though the CO cell is no longer operational. The CO detector
will not operate once the CO cell has reached its end of life.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
3
Symptoms
Mild headache
after 2-3 hours of exposure
Headache and nausea
after 1-2 hours of exposure
Headache, nausea, and dizziness
after 45 minutes of exposure;
collapse and unconsciousness
after 2 hours of exposure
Detector response time, min.
60-240
10-50
4-15
I56-6601-001
4/22/2019

Advertisement

loading