8300100104
VBH0310CTRLS

4.4 Connection diagram

No.
Conn.
Designation
CON1
L1, L2, L3
PE
PE
CON2
RSA
CON2
RSB
CON2
GND
CON2
IO1
CON2
IO2
CON2
IO3
CON2
Vout
CON2
COM
CON2
NC
LED
P1-IN
P3-OUT
Item no. 1170000606 · ENU · Change 0 · Approved 2021-12-16 · Page 10 / 16
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Function/assignment
Power supply, phase, see nameplate for voltage range
Protective earth
RS485 interface for MODBUS, RSA; SELV
RS485 interface for MODBUS, RSB; SELV
Reference ground for control interface, SELV
Function parameterizable (see "Optional interface functions" table)
Factory setting:
Digital input - high active, function: Disable input, SELV
- inactive: Pin open or applied voltage < 1.5 VDC
- active: applied voltage 3.5-50 VDC
Reset function: Triggering of error reset on change of state from "enabled" to "disabled"
Function parameterizable (see "Optional interface functions" table)
Factory setting:
Analog input 0-10 V / PWM, Ri=100 kΩ, function: Set value
Characteristic curve parameterizable (see input characteristic curve P1-IN), SELV
Function parameterizable (see "Optional interface functions" table)
Factory setting:
Analog output 0-10 V, max. 5 mA, function: Fan modulation level
Characteristic curve parameterizable (see output characteristic curve P3-OUT), SELV
Voltage output 3.3-24 VDC ±5%, Pmax=800 mW, voltage parameterizable
Factory setting: 10 VDC
short-circuit-proof, supply for external devices, SELV
alternatively: 15-50 VDC input for parameterization via MODBUS without line voltage
Status relay, floating status contact, common connection, contact rating 250 VAC / 2 A (AC1) / min. 10 mA,
reinforced insulation on supply side and on control interface side
Status relay, floating status contact, break for failure
green: status = good, ready for operation
orange: status = warning
red: status = failure
Input characteristic curve
Output characteristic curve