Connection Diagram - ebm-papst D3G146-LU03-30 Operating Instructions Manual

Table of Contents

Advertisement

D3G146-LU03-30

4.4 Connection diagram

Drawing preliminary!
No.
Conn.
Designation
CON10
10.1
PE
CON10
10.2
L
CON10
10.3
N
CON11
11.1
10 V/max. 1.1
mA
CON11
11.2
Tach
CON11
11.3
0-10 V PWM
CON11
11.4
GND
Item no. 53672-5-9970 · ENU · Change 230387 · Approved 2021-03-29 · Page 8 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Color
Function/assignment
green/
Protective earth
yellow
black
Power supply 230 VAC, 50-60 Hz, see nameplate for voltage range
blue
Neutral conductor
red
Voltage output 10 V, 1.1 mA, electrically isolated, not short-circuit-proof
white
Tach output: Open collector, 1 pulse per revolution, electrically isolated, Isink max = 10 mA
yellow
Control input 0-10 V or PWM, electrically isolated
blue
GND connection for control interface

Advertisement

Table of Contents
loading

Table of Contents