Wattstopper LMZC-301 - DLM Zone Controller Step-by-Step Installation Manual

Wattstopper LMZC-301 - DLM Zone Controller Step-by-Step Installation Manual

Also See for LMZC-301:

Advertisement

Wattstopper LMZC-301 - DLM Zone Controller Step-by-Step Installation Manual

SPECIFICATIONS

  • Input voltage - 115/277V 60 Hz
  • Class 2 connection to two independent DLM local networks (IRB)
    24VDC output, up to 250mA across 2 RJ45 ports per local network (A and B networks, 250 mA each)
    If using an optional LMRC-100 to boost output, the amount is 400 mA per network (two LMRC-100s needed if using both networks)
  • Free-topology DLM local network segments may include LMFC-011 Fixture Controllers, DLM switches, occupancy sensors, daylight sensors and input modules
  • Category 5e cable, up to 1,000 ft. total per local network
  • Terminals for connection to DLM segment network (BACnet MS/TP)
  • Segment network parameters
    • WattStopper LM-MSTP wire
    • Linear topology; 4000 ft. maximum per segment
  • Operating conditions:
    for indoor use only - 32-122 F (0 – 50 C) - 5-95% RH, non-condensing
  • UL and cUL listed

Installation

  • Step 1
    Remove the P115/277 board with the LMPI assembly
    Installation - Step 1
  • Step 2
    Mount the LMCZ-301, using 4 mounting screws.
    Installation - Step 2
  • Step 3
    Reinstall the P115/277 board with the LMPI assembly
    Installation - Step 3
    Note: If installing an optional LMRC-100s, attach it to the power supply board before reinstalling. See the instructions at the bottom of the following page.
  • Step 4
    Connect the incoming power cable to the power supply (and if used, to the LMRC-100).
    Installation - Step 4
    • Wiring for an LMRC-100
      Wiring for an LMRC-100

    • Wiring for two LMRC-100s
      Wiring for two LMRC-100s

  • Step 5
    Attach the ground wire.
    Installation - Step 5

  • Step 6
    Connect the Power Supply to the LMPI board.
    Installation - Step 6

  • Step 7

    Connect one or more LMRJ cables to the RJ45 jacks. There are two DLM IRB networks (labeled A & B) used to connect DLM devices such as the LMFC-011 Fixture Controllers, switches, sensors, and room controllers. The networks are labeled A and B. Each network has two RJ-45 jacks, for connecting CAT5 cable. It is not important which of the two jacks are used.
    Note: RJ45 jacks/Cat5 cables are only used to connect to DLM switches, sensors, room controllers, etc. to the panel. To connect one panel to another panel, use the MS/TP connectors
    Once installation is complete, re-attach the cover to the LMCZ-301.

Optional Installation of LMRC-100

In situations where a larger number of devices are connected to a DLM network, you can increase the amount of power output from the LMZC-301 by installing a powered room controller on either Cat 5e network (which adds power to just that network), or by installing one or two LMRC-100s within the unit (one per network). Secure the LMRC-100 to the power supply board on the LMZC-301, as shown to the right. Then, connect an LMRJ cable from the LMRC-100 to the LMZC-301.

Note: If using an LMRC-100, maximum operating condition is 104 F (40 C)

Note: An LMRC-100 should be only connected to Network A or B only. To use both Networks, you will need to install two LMRC-100s.

WARRANTY INFORMATION

WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.

2800 De La Cruz Boulevard
Santa Clara, CA 95050
Phone: 800-879-8585
www.wattstopper.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Wattstopper LMZC-301 - DLM Zone Controller Step-by-Step Installation Manual