THIS UNIT IS PRE-SET FOR PLUG n' GO™
OPERATION, ADJUSTMENT IS OPTIONAL.
For full operational details, adjustment and more
features of the product, see the DLM System Installation
Guide provided with the LMRC-102 room controller,
www.wattstopper.com
and also available at
FOR CONNECTION TO PLUG LOADS ONLY.
INSTALLATION SHALL BE IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS, LOCAL AND NEC CODES.
Wire connections shall be rated suitable for the wire
size (lead and building wiring) employed.
For Class 2 DLM devices and device wiring:
To be connected to a Class 2 power source only.
Do not reclassify and install as Class 1, or Power and Lighting Wiring.
WARNING: Do not install to cover a junction box having Class 1, 3 or
Power and Lighting Circuits.
PLACEMENT EXAMPLES
Line Voltage
(Class 1 wiring)
Plug Load
Controller
J-Box
To Plug Load
(Class 1 wiring)
To Other
Electrical
Outlets
MOUNTING THE CONTROLLER
The LMPL-101 controller can either be mounted external to
a junction box, placing it in the plenum space or mounted
directly inside a 4" x 4" junction box.
J-Box
Outside a 4" x 4" box
CONNECTIVITY
The LMPL-101 communicates with all other DLM devices
connected to the DLM local network. Connection drawings
are for example only. The low voltage LMRJ cables can
connect to any DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG.
WARNING:
TO CONNECT A COMPUTER TO THE DLM LOCAL
NETWORK USE THE LMCI-100. NEVER CONNECT THE DLM
LOCAL NETWORK TO AN ETHERNET PORT – IT MAY DAMAGE
COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Switch
Ceiling Mount
Occupancy
Sensor
J-Box
Inside a 4" x 4" box
Digital Lighting Management (DLM)
Digital Plug Load Room Controller
Input Voltage:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120VAC, 50/60Hz
Load Requirements:
Maximum Duplex Receptacle Rating . . . . . . . . . . . . . 120VAC, 20A
Output
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150mA @ 24VDC
DLM Local Network Characteristics for LMPL-101 or LMRC-10x:
Provides 24VDC power over Cat 5e cable and RJ-45 connectors
Supports up to 24 communicating devices, including 4
LMRC-10x or LMPL-101 controllers
Free topology up to 1,000ft of low voltage cable
Environment:
Operating Temperature. . . . . . . . . . . . . .32° to 104°F (0° to 40°C)
Storage Temperature . . . . . . . . . . . . . . 23° to 176°F (-5° to 80°C)
Relative Humidity. . . . . . . . . . . . . . . . . 5 to 95% (non condensing)
Patent Pending
Line Voltage
(Class 1 wiring)
Line Voltage
(Class 1 wiring)
Plug Load
Controller
J-Box
To Plug Load
(Class 1 wiring)
To Other
Electrical
Outlets
ATTACHING CABLES
Remove rubber jack covers if using all 3 RJ45 receptacles.
Leave covers in place for all unused receptacles.
Ceiling Mount
Low Voltage
Sensor
DLM Local Network
LMRJ Cables
Switch
LMPL-101
LMPL-101
Room
Controller
J-Box
To Lighting
Load
(Class 1 wiring)
Ceiling Mount
Occupancy
Sensor
Line
Voltage
Room
Controller
Red to
Load 1 (A)
LMRC
102
Yellow to
J-Box
Load 2 (B)
120VAC
Plug Load
Controller
White: Neutral
Red: Switched
120VAC Line
J-Box
Switch
Loads
1
2
Ground