York ZF150 Installation Manual page 24

Hide thumbs Also See for ZF150:
Table of Contents

Advertisement

518674-YIM-C-0610
ZF078-150 Standard Motor - With Powered Convenience Outlet
Compressors
(each)
Size
Volt
(Tons)
RLA LRA
MCC
208
9.3
68
14.5
230
9.3
68
14.5
078
(6.5)
460
4.9
34
7.7
575
3.8
28
6
208
11.9
88
18.5
230
11.9
88
18.5
090
(7.5)
460
5.2
44
8.1
575
4.8
36
7.5
208
12.2
88
19
230
12.2
88
19
102
(8.5)
460
5.8
44
9
575
4.4
36
5.5
24
OD Fan
Supply
Pwr
Pwr
Motors
Blower
Exh
Conv
(each)
Motor
Motor
Outlet
FLA
FLA
FLA
FLA
1.5
6.0
5.5
10
1.5
6.0
5.5
10
0.8
3.0
2.2
0.6
2.4
1.8
3.5
6.0
5.5
10
3.5
6.0
5.5
10
1.6
3.0
2.2
1.3
2.4
1.8
3.5
6.8
5.5
10
3.5
6.8
5.5
10
1.6
3.4
2.2
1.3
2.7
1.8
Electric Heat Option
Model
kW
Stages Amps
None
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18
2
50.0
E36
25.5
2
70.8
None
-
-
E09
9
1
22.6
E18
18
2
45.2
E24
24
2
60.2
E36
34
2
85.3
None
-
-
E09
9
1
11.3
5
E18
18
2
22.6
E24
24
2
30.1
E36
34
2
42.7
None
-
-
E09
9
1
4
E18
18
2
18.1
E24
24
2
24.1
E36
34
2
34.1
None
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18
2
50.0
E36
25.5
2
70.8
None
-
-
E09
9
1
22.6
E18
18
2
45.2
E24
24
2
60.2
E36
34
2
85.3
None
-
-
E09
9
1
11.3
5
E18
18
2
22.6
E24
24
2
30.1
E36
34
2
42.7
None
-
-
E09
9
1
4
E18
18
2
18.1
E24
24
2
24.1
E36
34
2
34.1
None
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18
2
50.0
E36
25.5
2
70.8
None
-
-
E09
9
1
22.6
E18
18
2
45.2
E24
24
2
60.2
E36
34
2
85.3
None
-
-
E09
9
1
11.3
5
E18
18
2
22.6
E24
24
2
30.1
E36
34
2
42.7
None
-
-
E09
9
1
4
E18
18
2
18.1
E24
24
2
24.1
E36
34
2
34.1
1
MCA
1
MCA
w/Pwr
(Amps)
Exh
(Amps)
-
40.1
45.6
43.6
50.5
66.8
73.7
82.5
89.3
108.5
115.4
-
40.1
45.6
47.1
53.9
74.1
81
92.2
99
122.2
129.1
-
20.7
22.9
23.5
26.3
37.1
39.8
46.1
48.8
61.1
63.9
-
16.2
18
9.0
18.8
21.1
29.7
31.9
36.9
39.1
48.9
51.1
-
49.8
55.3
49.8
55.3
66.8
73.7
82.5
89.3
108.5
115.4
-
49.8
55.3
49.8
55.3
74.1
81
92.2
99
122.2
129.1
-
22.9
25.1
23.5
26.3
37.1
39.8
46.1
48.8
61.1
63.9
-
19.8
21.6
9.0
19.8
21.6
29.7
31.9
36.9
39.1
48.9
51.1
-
51.3
56.8
51.3
56.8
67.8
74.7
83.5
90.3
109.5
116.4
-
51.3
56.8
51.3
56.8
75.1
82
93.2
100
123.2
130.1
-
24.7
26.9
24.7
26.9
37.6
40.3
46.6
49.3
61.6
64.4
-
19.2
21
9.0
19.2
21.5
30
32.3
37.2
39.5
49.3
51.5
Johnson Controls Unitary Products
2
Max Fuse
/
2
Max Fuse
/
3
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
60
70
80
90
90
110
125
50
50
50
60
80
90
100
100
125
150
25
25
25
30
40
40
50
50
70
70
20
20
20
25
30
35
40
40
50
60
60
60
60
60
70
80
90
90
110
125
60
60
60
60
80
90
100
100
125
150
25
30
25
30
40
40
50
50
70
70
20
25
20
25
30
35
40
40
50
60
60
60
60
60
70
80
90
100
110
125
60
60
60
60
80
90
100
100
125
150
30
30
30
30
40
45
50
50
70
70
20
25
20
25
30
35
40
40
50
60

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zf120Zf seriesZf102Zf090Zf078

Table of Contents