Siemens SITOP UPS1600 Getting Started page 26

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Parameterizing the SITOP UPS1600
6.1 Buffering an S7 IO controller, including the I/O when the power fails
4. Click on the symbols to open the "Device configuration" and select "Base Unit".
5. Check that the checkbox "Buffering allowed" is selected. Select it if it is deactivated.
Note
If the checkbox "Buffering allowed" is not selected, independent of the following entries,
there is no buffering.
6. For "Connection threshold", enter the voltage value, which, when it is fallen below the
26
UPS, starts to buffer.
SITOP UPS1600 under STEP 7 V13
Getting Started, 06/2014