Installation Procedure
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Install air ventilation to drain condensation smoothly.
• If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than
550 mm, there may be water leaks.
Band joint
• Do not give the hose an upward gradient beyond the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
14
English
Air ventilation
Ceiling
300 mm or less
20 mm or more
Drain hose
Ceiling
Under gradient
Ceiling
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Install horizontally.
Be horizontal
Indoor unit
• Max. allowable axis gap.
Indoor unit
• Max. allowable bending angle.
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
Full thread bolt hanger
Main drain pipe
Flexible hose
Max. 20 mm
Max. 30°
1000 to 1500 mm
Main air vent
(must be installed)
200 mm
or more
300 to
550 mm
Centralized horizontal drain pipe
(more than 1/100 slope)