Riello RS 130/M TC Instruction Manual page 14

Table of Contents

Advertisement

Available languages

Available languages

Installation
4
Securing the burner to the boiler
Before fixing the burner to the boiler, check from the open-
ing of the blast tube that the probe and the electrode are
correctly positioned, as in Fig. 12.
If, in the previous check, the position of the probe or elec-
trode was not correct, remove the screw 1)(Fig. 13),
extract the inner part 2)(Fig. 13) of the head, and adjust
them.
Do not rotate the probe: leave it as in Fig. 12 since if it is
located too close to the ignition electrode, the control box
amplifier may be damaged.
Separate the combustion head from the rest of the burner,
Fig. 11.
To do this, proceed as follows:
- loosen the 4 screws 3) and remove the hood 1);
- disengage the articulated coupling 7) from the gradu-
ated sector 8);
- remove screws 2) from the two slide bars 5);
- remove the 2 screws 4) and pull the burner back on
slide bars 5) by about 100 mm;
- disconnect the probe and electrode cables, then slide
off the burner completely from the slide bars.
Once this operation has been carried out, fix the flange
11)(Fig. 11) to the boiler plate, interposing the insulating
gasket 9)(Fig. 11) supplied.
Use the 4 screws supplied, with a tightening torque of 35 -
40 Nm, after protecting their thread with anti-seize prod-
ucts.
The seal between burner and boiler must be airtight. After
the start-up (see Ch. 5.3), check there is no leakage of flue
gases into the external environment.
20032905
Probe
D613
1
2
12
GB
Electrode
D8689
Fig. 12
Fig. 13

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Rs 130/m tl32583x39116x2003258320039116

Table of Contents