Service Manual
5.
Troubleshooting
for F0 malfunction
Heat exchangers are
too dirty or the air inlet/outlet
Compressor doesn't work
normally. Strange noise or leakage occurs.
Casing is too hot.
System is blocked inside
(dirt block, ice block, oil block, Y-valve no
fully open).
The refrigerant is leaking
Replace a main
board with the
same model.
Installation and Maintenance
Clean the heat exchangers
Yes
blockage of air inlet/outlet.
is blocked.
No
Make compressor run normally.
Yes
No
Yes
Remove blockage in the system
No
Check the leaking status of refrigerant
Yes
and charge refrigerant
No
End
and remove
Malfunction is
eliminated.
No
Malfunction is
eliminated.
No
Malfunction is
eliminated.
No
Malfunction is
eliminated.
No
Yes
Yes
Yes
Yes