Electrical Installation - Honeywell Midas S2 Quick Reference Manual

Fixed single-point extractive gas transmitter
Hide thumbs Also See for Midas S2:
Table of Contents

Advertisement

Electrical installation

Reference
TB1-(1)
TB1-(2)
TB2-(1)
TB2-(2)
TB3-(1)
TB3-(2)
TB3-(3)
TB3-(4)
TB3-(5)
TB3-(6)
NDIR/PYRO
Relay rating : 1.0A@30VDC or 0.5 A@125 VAC max.
TB2-(2)
TB2-(1)
TB1-(2)
TB1-(1)
Category
DC power
24Vdc input — VIN+
DC power
OVdc — VIN-
mA output
4-20mA analog output
mA output
COM
Relay1
Alarm1 – COM
Relay1
Alarm1 – NO/NC (default NO)
Relay2
Alarm2 – COM
Relay2
Alarm2 - NO/NC (default NO)
Relay3
Common Fault – COM
Relay3
Common Fault – NO/NC (default NO)
Pyrolyzer or NDIR connector
TB3-(1)
TB3-(2)
TB3-(3)
TB3-(4)
TB3-(5)
TB3-(6)
NDIR/
PYRO
Description
13

Advertisement

Table of Contents
loading

Table of Contents