Fluidwell F118-P Manual

Fluidwell F118-P Manual

Flow rate monitor / totalizer with linearization and high / low alarms
Hide thumbs Also See for F118-P:

Advertisement

Quick Links

F118-P
FLOW RATE MONITOR / TOTALIZER
WITH LINEARIZATION AND HIGH / LOW ALARMS
Signal input flowmeter: pulse, Namur and coil.
Signal outputs: (0)4-20mA / 0-10V ref. flow rate and pulse ref. total.
Alarm outputs: maximum three flow rate alarms
Options: Intrinsically Safe, Modbus communication
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F118-P

  • Page 1 Signal input flowmeter: pulse, Namur and coil. Signal outputs: (0)4-20mA / 0-10V ref. flow rate and pulse ref. total. Alarm outputs: maximum three flow rate alarms Options: Intrinsically Safe, Modbus communication F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    ▪ This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). ▪ Do connect a proper grounding to the metal enclosure as indicated if the F118-P has an incoming power line which carries a 115-230V AC. The Protective Earth (PE) wire may never be disconnected or removed.
  • Page 3: About The Manual

    This manual describes the standard unit as well as the available options. For additional information, please contact your supplier. A hazardous situation may occur if the F118-P is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this manual indicated by the pictograms: A "warning !"...
  • Page 4 Operational ..........................6 2.1. Control panel 2.3. Operator information and functions Configuration ..........................8 3.1. How to program the F118-P 3.1.1. Setup menu - Settings 3.1.2. Explanation of Setup menu 1 - Total 3.1.3. Explanation of Setup menu 2 - Flow rate 3.1.4.
  • Page 5: System Description

    Fig. 1: typical application Configuration of the unit The F118-P is designed for use in many types of applications. For that reason, a setup menu is available to program the F118-P according to your specific requirements. The setup includes several important features, such as K-Factors, engineering units, signal selection, power management (to extend battery life-time), etc.
  • Page 6: Control Panel

    • Take careful notice of the "Safety rules, instructions and precautionary measures" in the front of this manual. This chapter describes the daily use of the F118-P. This instruction is meant for users / operators. 2.1. CONTROL PANEL The control panel has three keys. The available keys are: Fig.
  • Page 7 ▪ How to program the alarm thresholds The F118-P can give an alarm message on the display. When set to on, at the same time, the digital outputs can give a signal for processing by an external device. Note that it is also possible to set or change the alarm thresholds from the setup menu.
  • Page 8 How to enter the setup menu When the setup menu is protected by a password, the F118-P asks for a password to access the setup menu. When in the operator mode, press and hold the PROG/ENTER key for 7 seconds to access the setup menu.
  • Page 9 The SELECT/ key and the CLEAR/ key are used for navigation. The explanation assumes that you are in the submenu TOTAL. When you are: • in the first setting and you navigate to the previous setting, the F118-P goes back to the related main menu.
  • Page 10 0.001 - 9 amount 0.001 - 9999999 COMMUNICATION speed 1200; 2400; 4800; 9600 address 1 - 247 mode bus-rtu; bus-asc; off OTHERS model F118-P software version nn:nn:nn serial no. nnnnnnn password 0000 - 9999 tag-nr 0000000 - 9999999 FW_F118P_v1901_02_EN.docx...
  • Page 11 Page 11 3.1.2. EXPLANATION OF SETUP MENU 1 - TOTAL This setting is used to select the engineering unit for the indication of the total, the UNIT accumulated total and the pulse output. When you change the engineering unit, you must recalculate and reprogram the K-factor for the (accumulated) total.
  • Page 12 3.1.4. EXPLANATION OF SETUP MENU 3 - ALARM These settings determine how the flow rate is monitored and how the F118-P will process the alarm conditions. For the setup of the configurable outputs, refer to setup menu: Relays. When the flow rate is zero, then it is possible to ignore or disable the flow rate FLOWZERO monitoring.
  • Page 13: Battery Mode

    When used with the internal battery option (type PB/PC), the user can expect reliable measurement over a long period of time. The F118-P has several smart power management functions to extend the battery life time significantly. Two of these functions can be set.
  • Page 14 Page 14 FREQUENCY / The frequency is shown at the bottom line of the display. The maximum M-FACTOR frequency is 9999.9 Hz. With value 0.0Hz, the M-Factor is disabled. The M- 71 TO 7A Factor (MF) is shown at the top-line of the display. The minimum value to be entered is 0.000001 and the maximum value is 9.999999.
  • Page 15 Page 15 TUNE-MIN The (0)4mA or 0V value can be tuned precisely with this setting. The initial minimum analog output value is (0)4mA or 0V. However, this value might differ slightly due to ambient influences such as temperature for example. Before tuning the signal, make sure that the analog signal is idle (not used) for any application! After pressing PROG, the current will be about 4mA (0mA or 0V).
  • Page 16 3.1.11. EXPLANATION OF SETUP MENU B - OTHERS For support and maintenance it is important to have information about the characteristics of the F118-P . Your supplier will ask for this information when support is required. MODEL This setting shows the model name.
  • Page 17: Installation / Surrounding Conditions

    When used in very cold surroundings or varying climatic conditions, inside the instrument case, take the necessary precautions against moisture. Mount the F118-P onto a solid structure to avoid vibrations. For use in Safe and Hazardous Areas (or Locations), the following conditions apply: Relative humidity: <...
  • Page 18: Dimensions- Enclosure

    Page 18 4.3. DIMENSIONS- ENCLOSURE Aluminum and stainless enclosures (where “H” turns to “HS” for stainless, e.g. HA → HSA): 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm...
  • Page 19 Page 19 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12” 0.12” D=22mm (0.866") 3x D=22mm (0.866”) 29.1 mm (1.15”)
  • Page 20: Installing The Hardware

    4.4.1. GENERAL INSTALLATION GUIDELINES • The F118-P that came with a power module type PM; 110V-230V AC or type PD/PF with an option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel. The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers.
  • Page 21: Protective Earth (Pe) Connections

    Metal enclosure When the F118-P is supplied with a metal enclosure (aluminum or stainless steel), the enclosure must be grounded in accordance with national and local electrical codes. To ground the field mounted unit, the PE conductor must be connected to the PE stud which is located in the metal back cover, as indicated in the image below.
  • Page 22 Do not use the terminal 00 to connect the protective earth wire, the 00 and the common ground terminals are internally connected. Be careful, to prevent damage to equipment when you connect different power supplies (sensor, PLC, etc.). Inside the Fluidwell display, the common grounds are internally connected to each other.
  • Page 23 Page 23 4.4.5. PLASTIC (GRP) ENCLOSURE The PE connection The F118-P in a GRP enclosure meets the requirements of class 2 (double insulated). Therefore the incoming PE wire is terminated with an insulating end cap. Type PM (110-230V AC) Type OR (8-24V AC) Type OR (8-30V DC) FW_F118P_v1901_02_EN.docx...
  • Page 24: Terminal Connectors

    Set the sensor supply 1. Make the F118-P safe. If applicable, mind the battery power. 2. Open the F118-P and carefully remove the cable-connectors and the protective cover. 3. Find and set the switches and select the V as required.
  • Page 25 Page 25 Risk of electrocution - High voltage! Make sure, all the leads to the terminals are disconnected from the F118-P and NEVER connect the mains power supply to the unit when the protection cover has been removed! Type PD...
  • Page 26 Page 26 Type OR: A mechanical relay output flow rate alarm output or pulse output is available with this option. Max. switch power 240V 0.5A per output. (Requires power supply type PD/PF/PM). Fig. 11: Terminal connections - Mechanical relay output (typical) Type OT: A passive transistor output is available with this option.
  • Page 27 Page 27 Type AB: An active 0-20mA signal proportional to the flow rate is available with this option. Max. driving capacity 1000 Ohm @ 24VDC. (Requires power supply type PD/PF/PM). Fig. 14: Terminal connections - Active 0-20mA analog output (typical) Type AF: For the Intrinsically Safe floating 4-20mA signal: please read Chapter 5.
  • Page 28 Fig. 18: Terminal connections - Coil signal input (typical) Pulse-signal NPN / NPN-LP: The F118-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency - read par.
  • Page 29 Pulse-signal PNP / PNP-LP: The F118-P is suitable for use with flowmeters which have a PNP output signal. 3V is offered on terminal 11 which has to be switched by the sensor to terminal 10 (SIGNAL). For a reliable pulse detection, the pulse amplitude has to go above 1.2V.
  • Page 30 Page 30 NAMUR-signal: The F118-P is suitable for flowmeters with an Namur signal. The standard F118-P is not able to power the Namur sensor, as an external power supply for the sensor is required. However, a 8.2V sensor supply voltage (terminal 11) can be provided via types PD-PM.
  • Page 31: Intrinsically Safe Applications

    Please note • Certificates, safety values, control drawing and declaration of conformity can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic safety”. • When installing this device in hazardous areas, the wiring and installation must comply with the appropriate installation standards for your industry.
  • Page 32 Page 32 Serial number and year of production This information can be looked-up in the setup menu: Others. Fig. 26: Example serial number (typical) Label information pulse input type – F1xx-..-..-XI (inside and outside the enclosure) Fig. 27: Label information - Intrinsic safe application (typical) FW_F118P_v1901_02_EN.docx...
  • Page 33 3 and 4 and/or terminals 5 and 6; the maximum values for any of those circuits are those as defined for group IIB/IIIC. Terminal connectors F118-P-XI: For intrinsically safe applications, consult the safety values in the certificate.
  • Page 34 5. Close the F118-P. Risk of electrocution - High voltage! Make sure, all the leads to the terminals are disconnected from the F118-P and NEVER connect the mains power supply to the unit when the protection cover has been removed! Type PD-XI Power supply in: 16-30V DC / max.
  • Page 35: Configuration Examples

    Page 35 CONFIGURATION EXAMPLES Fig. 31: F118-P-(AP)-(CT)-(OT)-PC-XI - Battery powered - IIB/IIC – IIIC FW_F118P_v1901_02_EN.docx...
  • Page 36 Page 36 Fig. 32: F118-P-AP-(CT)-OT-(PX)-XI - Output loop powered - IIB/IIC - IIIC FW_F118P_v1901_02_EN.docx...
  • Page 37: Remove The Battery

    Page 37 BATTERY REPLACEMENT INSTRUCTIONS 5.3.1. SAFETY INSTRUCTIONS • Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. • Only use batteries which are certified for use in hazardous areas. The use of standard batteries in hazardous area's is not safe and prohibited.
  • Page 38: Maintenance

    Repairs should only be carried out by the manufacturer or his authorized agent. 6.3. REPAIR POLICY If you have any problem with your Fluidwell product and you wish to repair it, please follow the procedure below: a. Obtain a Return Material Authorization (RMA) from your supplier or distributor Together with the RMA, you need to complete a repair form to submit detailed information about the problem.
  • Page 39: Appendix A: Technical Specification

    Page 39 APPENDIX A: TECHNICAL SPECIFICATION General Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB LCD with LED backlight.
  • Page 40 Page 40 Sensor excitation Type PB / PC / PX 3V DC for low power pulse signals and 1.2V DC for coil pick-up. Type PD 1.2; 3; 8.2; 12; 24V DC - max. 50mA@24V DC Type PD-XI Intrinsically safe: Pulse signals: 1.2; 3; 8.2 - max. 7mA@8.2V DC. Type PF / PM 1.2;...
  • Page 41 Page 41 Communication option Protocol bus-rtu; bus-asc Speed 1200; 2400; 4800; 9600 Addressing 1 - 247 Type CB RS232 Type CH RS485 2-wire Type CI RS485 4-wire Type CT TTL Intrinsically safe communication. Type CX no communication. Operational Operator functions Displayed functions •...
  • Page 42: Appendix B: Problem Solving

    Page 42 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F113-P is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check: ▪ Signal selection; ▪ Pulse amplitude;...
  • Page 43: Appendix C: Communication Variables

    Page 43 APPENDIX C: COMMUNICATION VARIABLES General The product is fitted with the Modbus communication protocol and can be equipped with various physical interfaces like RS485 and RS232 (please see device datasheet for available options). The tables below show the various variables that can be accessed through the communication. Currently, the function codes supported are: •...
  • Page 44 Page 44 Setup variables REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS TOTAL REGISTERS [d] 32 40033 unit uint16 0=none 3=kg 6= USGAL [h] 0x020 4= lb 7=bbl 2= m 5=GAL [d] 33 40034 decimals uint16 0…3 [h] 0x021 [d] 34 40035 K-Factor uint32 1...9999999...
  • Page 45 Page 45 REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS LINEARIZATION REGISTERS [d] 1024 41025 linearization table entry struct The linearization table is an INDEXED [h] 0x400 variable. Reading and writing the entries of the uint24 linearization tables is done by first selecting the entry through the index.
  • Page 46 Page 46 REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS COMMUNICATION REGISTERS [d] 144 40145 speed (Baudrate) uint16 0=1200 1=2400 2=4800 3=9600 [h] 0x090 [d] 145 40146 Modbus address uint16 1…247 [h] 0x091 [d] 146 40147 Modbus mode uint16 0: ASCII 1: RTU 2: OFF [h] 0x092...
  • Page 47: Declaration Of Conformity

    Page 47 APPENDIX D. DECLARATION OF CONFORMITY FW_F118P_v1901_02_EN.docx...
  • Page 48 Page 48 INDEX OF THIS MANUAL accumulated Total ........7 Intrinsic safety ........31, 33 actual settings ..........50 Intrinsically Safe options ......34 analog IP classification.......... 17 floating output..........34 Low-battery alarm ........7 flowrate min..........14 maintenance ..........
  • Page 49 Fig. 29: Terminal connections - Intrinsic safe floating 4-20mA analog output (typical) ..... 34 Fig. 30: Switch position voltage selection type PD-XI ................ 34 Fig. 31: F118-P-(AP)-(CT)-(OT)-PC-XI - Battery powered - IIB/IIC – IIIC .......... 35 Fig. 32: F118-P-AP-(CT)-OT-(PX)-XI - Output loop powered - IIB/IIC - IIIC ........36 FW_F118P_v1901_02_EN.docx...
  • Page 50: List Of Configuration Settings

    Page 50 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - TOTAL Enter your settings here 11 unit 12 decimals 0000000 13 K-factor 0000001 14 decs K-fact 2 - FLOWRATE 21 unit 22 time /min 23 decimals 0000000 24 K-factor 0000001...
  • Page 51 94 width 0.000 95 decimals 96 amount 0001000 A - COMMUNICATION A1 speed (baudrate) 9600 A2 address A3 mode bus-rtu B - OTHERS B1 model F118-P B2 s-version 03.01.xx B3 serial nr xxxxxxx B4 password 0000 B5 tagnr 0000000 FW_F118P_v1901_02_EN.docx...
  • Page 52 Page 52 Fluidwell B.V. FW_F118P_v1901_02_EN.docx PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives the Netherlands the Netherlands © 2021 Fluidwell B.V.: FW_F118P_v1901_02_EN.docx...