Download Print this page

Greenheck SQ Mixed Flow Quick Start Manual page 2

Square duct adapter

Advertisement

Quick Start Guide
SQ MIXED FLOW FILTRATION
Filter sections are shipped
separate from the fan and are
mounted in the field
This Quick Start Guide does not
replace the Installation Operation
Manual (IOM), refer to the IOM for
more information
Parts List
(1) Fan
(1) Filter section
(1) Hardware kit
(2) Isolator kit (optional)
Tools List
Impact Driver
1/2 inch socket
Torque wrench
NOTE: Square Duct Adapter information on reverse side
ASSEMBLY VIDEO
SQ MIXED FLOW IOM
Step 1 - Mount Filter Section to Fan
Filter section and fan have "Airflow" decals on the
exterior of the units, ensure the arrows are aligned with
the airflow
Mount the filter section to the inlet of the fan using
appropriate number of provided 5/16 inch semi-gimlet
fasteners provided in hardware kit (no nuts required)
Tighten to 132 in∙lbs (11 ft·lbs) as specified in the IOM
with 1/2 inch socket DO NOT OVER-TIGHTEN
Fan sizing and performance is designed for the filter
section to be mounted directly to the
INLET of the fan
Step 2 - Install Filter and Fan Assembly in Ductwork
Install assembly in proper orientation for application (use
appropriate isolators)
Mount assembly to ductwork using fasteners supplied
by others
Assembly can be mounted in horizontal or vertical
applications
Flexible duct connectors are recommended for
mounting to the inlet of the filter section and outlet of
the fan
Install assembly with approximately three wheel
diameters of straight duct before and after the fan
Step 3 - Filter Replacement and Cleaning
Follow filter replacement and or cleaning intervals
recommended by filter supplier
1. Remove access door using 1/2 inch socket
It is only necessary to remove one access door to
replace filters
2. Remove filter spacers and dirty filters
3. Install new filters in unit and replace filter spacers
Ensure filters are installed in correct orientation for
proper airflow (marked on filters)
Locate spacers towards the outside of the unit to
reduce any unnecessary blockage in airflow
4. Reinstall access door using 1/2 inch socket, torque to
132 in∙lbs (11 ft·lbs) DO NOT OVER-TIGHTEN
FILTER(S)
485551 • Square Duct Adapter and Filtration, Rev. 2, August 2023 • Copyright © 2023 Greenheck Fan Corp.
FILTER(S)
FILTER
SPACER(S)

Advertisement