Connect Power Cable - Graco 24K335 Instructions Manual

Air compressor and receiver tank for reactor e-30i and e-xp2i integrated plural component proportioning systems

Advertisement

Connect Power Cable

Note
Reference wiring diagram. See
Fig. 4, page 6.
1. Turn off the 120/240 VAC alternator circuit
breaker (CB10).
Figure 2
2. Loosen screw, below the air compressor
electrical enclosure (E), 1/4 turn until the cover is
loose. Remove cover.
3. Discard washer on the cord grip (35). Install
cord grip up through the bottom of the enclosure
knockout. Tighten cord grip mounting nut inside
the enclosure.
4. Loosen the outside nut on the cord grip (35).
Insert the end of the power cable (34) with shorter
strip lengths through the cord grip.
5. Connect the black wire to terminal 1/L1 and the
white wire to 3/L2.
6. Loosen ground screw and connect ground wire
with existing ground wire.
3A1902C
7. Tighten the bottom nut on the cord grip (35).
8. Replace cover. See Fig. 4, page 5.
9. Loosen the bolts and remove the back panel of
10. Use a screw driver to punch out a knockout.
11. Discard washer from cord grip (35). Install cord
12. Loosen the nut on the cord grip (35). Insert the
13. Connect the black and white wire to CB04,
14. Tighten nut on the cord grip (35).
15. Turn CB04 on. See Fig. 4, page 5.
16. Turn on the 120/240 VAC alternator circuit
Get other manuals https://www.bkmanuals.com
Connect Power Cable
the Reactor electrical enclosure.
grip through back panel.
free end of the power cord (34) through the cord
grip.
see Fig. 4, page 5. Connect the green wire to
the ground bus bar, GB02 inside the Reactor
electrical enclosure.
breaker (CB10).
Figure 3
5