Watts iDROSET CSD Series Installation Instructions
Watts iDROSET CSD Series Installation Instructions

Watts iDROSET CSD Series Installation Instructions

Static balancing valves with calibrated flow measurement

Advertisement

Available languages

Available languages

Quick Links

Installation Instructions
iDROSET
Static Balancing Valves with Calibrated Flow Measurement
Sizes:
- 2"
1
2
WARNING
!
Installation
1. Before installation, verify the correct size LFiDROSET
CSD has been selected for the application. Be sure to
review all operating parameter specifications found on
the ES document to ensure the valve is fit for the appli­
cation.
2. The system must be thoroughly flushed to remove dirt
and debris before installing the valve. For retrofit appli­
cations, it is recommended that a wye strainer (such as
the Watts LF777SI) be installed. LFiDROSET hardware
kit comes with strainer. Install immediately upstream of
the valve.
3. The valve is directional – see flow direction arrow on back of valve.
4. The valve should be installed in an accessible location with the gauge positioned for easy
reading.
5. For maximum accuracy, the flow measurement valve should be located in an unrestricted
straight pipe run so that no fittings (elbow, valve, tee, etc.) is closer to the measurement
valve than 5 pipe diameters upstream and 2 pipe diameter downstream. If a balancing
valve is located downsteam from a circulation pump, allow a distance of ten (10) diameters
between the pump and balancing valves.
System Commissioning & Balancing
1. Upon commissioning of the system, open the valve completely by turning hand wheel full
counter-clockwise.
2. During the balancing process, adjust the desired flow rate in GPM according to the project
data. Turn the wheel counter-clockwise to increase the flow and clockwise to decrease the
flow.
3. Once the balancing process is complete, tighten the screw to lock the hand wheel with a
3mm Allen key. For future reference and to aid system diagnostics, set the red pointer to
the desired flow rate.
Maintenance
1. It is recommended that the valve be fully opened and closed at least twice a year to
ensure it is free of dirt and debris and (if
equipped) the wye strainer be serviced.
/LFiDROSET
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death,
serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
Series CSD

Advertisement

loading

Summary of Contents for Watts iDROSET CSD Series

  • Page 1 2. The system must be thoroughly flushed to remove dirt and debris before installing the valve. For retrofit appli­ cations, it is recommended that a wye strainer (such as the Watts LF777SI) be installed. LFiDROSET hardware kit comes with strainer. Install immediately upstream of the valve.
  • Page 2 2. Antes de instalar la válvula, lave minuciosamente el sistema para eliminar la suciedad y los residuos. Para aplicaciones de retroadaptación, se recomienda instalar un filtro en bifurcación (como el LF777SI de Watts) inmediatamente aguas arriba de la válvula. El juego de herramientas LFiDROSET incluye un filtro en Y.
  • Page 3 Pour les applications de modernisation, il est recommandé d’installer une crépine en Y (comme le modèle Watts LF777SI) immédiatement en amont du robinet. La trousse de quincaillerie LFiDROSET comprend une crépine.
  • Page 4 ORIGINAL. Garantie limitée : Watts Regulator Co. (la « Société ») garantit que chacun de ses produits est exempt de vice de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à compter de la date d’expédition d’origine. Dans l’éventualité où de tels vices se manifesteraient pendant la période de garantie, la Société, à...

This manual is also suitable for:

Lfidroset csd seriesIdroset csd-050Idroset csd-075Idroset csd-100Idroset csd-125Idroset csd-150 ... Show all