Rotational Speed Limit Values; Voltage And Frequency Fluctuations During Line Operation; Phase Synchronization During Supply System Switching; System-Inherent Frequencies - Siemens SIMOTICS FD 1LL1 Operating Instructions Manual

Low-voltage motor
Table of Contents

Advertisement

4.12

Rotational speed limit values

Excessive rotational speed can lead to serious damage to the machine. This can result in
death, serious injury, or material damage.
● Avoid operation above the permissible speed by using the appropriate control function.
● Observe the speeds stamped on the rating plate.
4.13

Voltage and frequency fluctuations during line operation

Unless otherwise stated on the rating plate, the permissible voltage/frequency fluctuation is
corresponds to Zone B in IEC / EN 60034‑1. Permissible fluctuations that go beyond this are
indicated on the rating plate.
Operate the machine in continuous operation in Zone A. Prolonged operation in Zone B is not
recommended:
● Exceeding the permissible tolerances for voltage and frequency can lead to an
● Limit exceptions of this sort with regard to the values that arise, how often, and for how long
● Where possible and within a reasonable time take corrective actions such as reducing the
4.14

Phase synchronization during supply system switching

Damage to the machine may be caused when switching to another supply system with different
phasing.
● The phasing must be synchronized during switching. Use appropriate means to
4.15

System-inherent frequencies

Excessively high vibration levels and system resonances can damage the machine set.
● Configure and match the system consisting of the foundation and machine set in such a way
● The vibration values according to DIN ISO 10816-3 must not be exceeded.
SIMOTICS FD 1LL1
Operating Instructions 01/2019
impermissibly high temperature rise of the winding. This can result in long-term damage to
the winding.
they occur.
power. In this way you can avoid that the service life of the machine is reduced as a result
of thermal aging.
synchronize the phasing.
that no system resonances can arise and result in the permissible vibration levels being
exceeded.
Preparations for use
4.12 Rotational speed limit values
33

Advertisement

Table of Contents
loading

Table of Contents