AQ250 SERIES HYDRONIC CONTROL PANELS
Table 3. AQ15540B Zoning Module (Pump Zoning Module) DIP Switch Arrangement.
DIP
Switc
h
1
Zone Address: The positions of these 4 DIP switches define the unique address for
2
each zone on the AQUATROL network. For each group of 4 zones, there can be
3
only one DIP switch in the right hand (On) position.
4
The correct DIP switch settings for each zone module are:
• First Zone (1-4) Module:
• Second Zone (5-8) Module: 2 = ON position; 1, 3, and 4 = OFF position
• Third Zone (9-12) Module: 3 = ON position; 1, 2, and 4 = OFF position
• Fourth Zone (13-16) Module: 4 = ON position; 1, 2, and 3 = OFF position
5
• If set to SYNC, zone synchronization is enabled.
• If set to NOT, zone synchronization is disabled.
6
• If zone valves are normally closed (N.C.), set the NC/NO DIP switch to the Off
position.
• If zone valves are normally open (N.O.), set the NC/NO DIP switch to the On
position.
7
• If set to Group (ON position), the AUX Pump contacts on the Control Module
are switched when any of the zones on this Zoning Module are active.
• If set to - (OFF position), the AUX Pump contacts are not affected by activity on
these zones.
8
• If set to 2-Stg (ON position), then 2-stage operation is activated on thermostat
inputs. The zoning module operates as two 2-stage zones or 3 zones (one 2-
stage and two 1-stage).
• If set to 1-Stg (OFF position), then operates as four 1-stage zones.
a
The AQ15000B Boiler Control Module DIP switch #5 must be set to GROUP position and DIP switch #6 must be set to MAIN position.
68-0306—07
Switch Description
1 = ON position; 2, 3, and 4 = OFF position
16
Label and Factory Settings
AQ15540B
a
M23720A
Diagnostic
Test
Test
M34972