Surge protection devices

Advertisement

Quick Links

INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Surge Protection Devices
FSPD, TPS4 03, TPS4 09,
TPS4 11
usa.siemens.com/spd

Advertisement

loading

Summary of Contents for Siemens FSPD

  • Page 1 INSTALLATION, OPERATION AND MAINTENANCE MANUAL Surge Protection Devices FSPD, TPS4 03, TPS4 09, TPS4 11 usa.siemens.com/spd...
  • Page 2: Installation Instructions

    FSPD, TPS4 03, TPS4 09, TPS4 11 TPS4 03, TPS4 09, TPS4 11 Installation Instructions DANGER Hazardous Voltage Will cause death or serious injury. Turn off power before working on this equipment WARNING Safety First – Hazardous Voltage and Shock Hazard •...
  • Page 3 Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any obvious shipping damages. If any damage was found and is a result of shipping or handling, immediately file a claim with the shipping company and contact Siemens customer support.
  • Page 4 FSPD, TPS4 03, TPS4 09, TPS4 11 TPS4 09 Catalog Logic TPS4 Catalog No. Voltage Code Surge Current (kA) Options A = 120/240 V, 1Ø, 3W 13 = 130 kA per phase E = Extended B = 120/240 V, 3Ø, 4W...
  • Page 5 Line Side versus Load Side Installation The FSPD Series is tested and qualified as a Type 2 SPD per UL 1449 4th Ed. The TPS4 03 and 09 series are tested and qualified as a Type 1 SPD. This SPD can be installed on the Line Side of the service overcurrent device. Type 1 SPDs may also be installed in UL Type 2 applications.
  • Page 6: Installation

    FSPD, TPS4 03, TPS4 09, TPS4 11 Retro-fit Into Existing Panel with No Available Breaker Positions Follow all applicable Codes: Consider consolidating loads in a manner that might free breaker positions. A ten foot tap rule in NEC® 240.21(B)(1) allows you to tap the bus as long as the tap conductors are rated at least 10% of the ampacity of the panel.
  • Page 7: Operation

    FSPD, TPS4 03, TPS4 09, TPS4 11 Operation LED Operation Each SPD contains 1 green LED per phase shown in the appropriate voltage configuration. When the LEDs are green complete protection is present. Upon MOV stack failure the LED corresponding to the failed mode will extinguish.
  • Page 8 3617 Parkway Ln only, and its effectiveness will be subject to specific variables including Peachtree Corners, GA 30092 field conditions and project parameters. Siemens reserves the right to United States of America modify the technology and product specifications in its sole discretion Telephone: +1 (800) 333-7421 without advance notice.