12 - FACTORY OPTIONS AND ACCESSORIES
■ Finally, raise the hoods and secure the side parts.
Left-hand
panels
10x30 hex screws
Electrical connection to be made by the costumer:
Note: see the wiring diagram included with the unit for a more
detailed information about the wiring.
The connection is done trought the left-hand panels (front view).
Initial location of the cables for connection:
50FF/FC unit
RP 052 to 062
Electric
panel
5
4
3
2
BOX6
1
TP
Connection to be made by the customer:
50FF/FC unit
RP 052 to 062
Electric
panel
5
4
3
2
BOX6
1
TP
12.7 - Air fi lters
The access panel to the fi lters incorporates dual locks, they can
function as hinges or can be used to remove the panel.
Note: Check that the locks are not blocked. Open them with a 4
mm Allen wrench (in an anti-clockwise direction).
"Standard" assemblies
Access panel
Return fans
module
BOX6
Damper
servo
W60TP
5
W33TP
4
S1
3
Return probe
W68TP
2
VR2
W67TP
1
VR1
Return fans
module
BOX6
Damper
servo
W60TP
5
W33TP
4
3
S1
Return probe
2
W68TP
VR2
W67TP
1
VR1
Access panel
■ These units include G4 gravimetric fi lters standard type, which
can be replaced by:
- G4 gravimetric fi lters with low pressure drop.
- G4 gravimetric fi lters standard type + M6, F7 or F9 folded
opacimetric fi lters.
- G4 gravimetric fi lters with low pressure drop + F7 or F9 folded
opacimetric fi lters.
- Double stage of folded opacimetric fi lters (M6+F7, M6+F9,
F7+F9 or F9+F9).
■ The width of the frames is 24 mm for the G4 standard type and
48 mm for the G4 low pressure drop and all opacimetric fi lters.
Important: G4 fi lters standard type supplied from the factory
cannot be replaced by other types of filters because the
thickness of the frames is diff erent.
When the factory-selected frames combination has less than
98 mm width, the structure incorporates a tensioner to lock the
position of the frames.
To extract the frames it is necessary to loosen the screws
securing the tensioner.
Note: the fi lters cleaning procedure is explained in the chapter of
"Maintenance"
"In-line" assemblies