Checking The Refrigerant Piping; About Checking The Refrigerant Piping; Precautions When Checking The Refrigerant Piping - Daikin 2MXM50A2V1B Installer's Reference Manual

Hide thumbs Also See for 2MXM50A2V1B:
Table of Contents

Advertisement

7
|
Piping installation

7.3 Checking the refrigerant piping

7.3.1 About checking the refrigerant piping

7.3.2 Precautions when checking the refrigerant piping

Installer reference guide
40
1 Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
a
b
a
b
a Liquid stop valve
b Gas stop valve
c Service port
2 Connect the gas refrigerant connection from the indoor unit to the gas stop
valve of the outdoor unit.
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is
installed in a ducting or the refrigerant piping is wrapped with finishing tape.
The outdoor unit's internal refrigerant piping has been factory tested for leaks. You
only have to check the outdoor unit's external refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor unit and the
indoor unit.
Typical workflow
Checking the refrigerant piping typically consists of the following stages:
1
Checking for leaks in the refrigerant piping.
2
Performing vacuum drying to remove all moisture, air or nitrogen from the
refrigerant piping.
If there is a possibility of moisture being present in the refrigerant piping (for
example, water may have entered the piping), first carry out the vacuum drying
procedure below until all moisture has been removed.
INFORMATION
Also read the precautions and requirements in the following chapters:
"2 General safety
"7.1 Preparing refrigerant
c
precautions" [
4
 7]
4
piping" [
 32]
2MXM40+50A
R32 Split series
4P600463-4E – 2021.12

Advertisement

Table of Contents
loading

This manual is also suitable for:

2mxm40a2v1b2mxm-a

Table of Contents