Cisco Nexus 3600 Hardware Installation Manual page 26

Table of Contents

Advertisement

Installing the Switch Using the NCS-1RU-ACC-KIT Rack-Mount Kit
3. If you are not installing the chassis into a grounded rack, you must attach a customer-supplied grounding
wire to the chassis as explained in the
the chassis into a grounded rack, you can skip this step.
4. Install the slider rails on the rack or cabinet as follows:
5. Insert the switch into the rack and attach it as follows:
6. If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the
facility ground.
DETAILED STEPS
Step 1
Install two front-mount brackets to the switch as follows:
a) Determine which end of the chassis is to be located in the cold aisle as follows:
• If the switch has port-side intake modules (fan modules with burgundy coloring), position the switch so that its
ports will be in the cold aisle.
• If the switch has port-side exhaust modules (fan modules with blue coloring), position the switch so that its fan
and power supply modules will be in the cold aisle.
b) Position a front-mount bracket so that four of its screw holes are aligned to the screw holes on the side of the chassis.
Note
Cisco Nexus 3600 Hardware Installation Guide
18
You can align any four of the holes in the front rack-mount bracket to four of the six screw holes on the
side of the chassis (see the two ways to mount these brackets on a typical chassis, in following figure).
The holes that you use depend on the requirements of your rack and the amount of clearance required
for interface cables (3 inches [7.6 mm] minimum) and module handles (1 inch [2.5 mm] minimum).
Grounding the Chassis, on page 29
Installing the Chassis
section.. If you are installing