Troubleshooting M.1. Troubleshooting Tips - Friedrich KCS12 Installation And Operation Manual

Table of Contents

Advertisement

M. TROUBLESHOOTING
M.1. Troubleshooting Tips
COMPLAINT
Unit does not operate.
Unit Trips Circuit Breaker or
Blows Fuses.
LCDI Power Cord Trips
(Reset Button Pops Out).
Unit Does Not Cool/ Heat Room
Sufficiently, or Cycles On And Off
Too Frequently.
46
CAUSE
The unit is turned to the off position, or the
thermostat is satisfied.
The LCDI power cord is unplugged.
The LCDI power cord has tripped (Reset
button has popped out).
The circuit breaker has tripped or the
supply circuit fuse has blown.
There has been a local power failure.
Other appliances are being used on the
same circuit.
An extension cord is being used.
The circuit breaker or time-delay fuse is
not of the proper rating.
The LCDI power cord can trip (Reset
button pops out) due to disturbances on
your power supply line.
Electrical overload, overheating, or cord
pinching can trip (Reset button pops out)
the LCDI power cord.
NOTE:
A damaged power supply cord must be replaced with a new power supply cord obtained from the product manu-
facturer and must not be repaired. The power cord must be replaced by trained service personnel.
The return/ discharge air grille is blocked.
Windows or doors to the outside are open.
The temperature is not set at a cool
enough/ warm enough setting.
The filter is dirty or obstructed.
The indoor coil or outdoor coil is dirty or
obstructed.
There is excessive heat or moisture
(cooking, showers, etc.) in the room.
The temperature of the room you are
trying to cool is extremely hot.
SOLUTION
Turn the unit to the on position and raise or lower temperature
setting (as appropriate) to call for operation.
Plug into a properly grounded 3 prong receptacle. See "Electrical
Rating Tables" on Page 6 for the proper receptacle type for your
unit.
Press and release RESET (Listen for click. Reset button latches
and remains in.) to resume operation.
Reset the circuit breaker, or replace the fuse as applicable. If
the problem continues, contact a licensed electrician.
The unit will resume normal operation once power has been
restored.
The unit requires a dedicated outlet circuit, not shared with other
appliances.
Do NOT use an extension cord with this or any other air condition-
er.
Replace with a circuit breaker or time-delay fuse of the proper
rating. See Table E.1 for the proper circuit breaker/ fuse rating for
your unit. If the problem continues, contact a licensed electrician.
Press and release RESET (Listen for click. Reset button latches
and remains in.) to resume normal operation.
Once the problem has been determined and corrected, press
and release RESET (Listen for click. Reset button latches
and remains in.) to resume normal operation.
Ensure that the return and/ or discharge air paths are not blocked
by curtains, blinds, furniture, etc.
Ensure that all windows and doors are closed.
Adjust the Temperature control to a cooler or warmer setting as
necessary.
Clean the filter, (see Routine Maintenance), or remove obstruction.
Clean the coils, (see Routine Maintenance), or remove obstruction.
Be sure to use exhaust vent fans while cooking or bathing and,
if possible, try not to use heat producing appliances during the
hottest part of the day.
Allow additional time for the air conditioner to cool off a very hot
room.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kuhl seriesKcm24Kcl28Kcl36Khs10

Table of Contents