SANJIANG SEC1000 Installation & Commissioning Manual

SANJIANG SEC1000 Installation & Commissioning Manual

Fire alarm control panel

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for SANJIANG SEC1000

  • Page 2: Table Of Contents

    SEC1000 FIRE ALARM CONTROL PANEL DOC NO. EM30165200200907/V1.0 CONTENTS 1. About This Manual............................2 2. Introduction..............................2 2.1 Overview............................. 2 2.2 Technical Specifications........................2 3. Installation and Connections........................3 3.1 Panel’s interior........................... 3 3.2 Internal wiring............................ 5 3.3 Mounting the chassis to the wall....................5 3.4 Mains connection..........................
  • Page 3: About This Manual

    2. Introduction 2.1 Overview The purpose of the SEC1000 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.
  • Page 4: Installation And Connections

    SEC1000 FIRE ALARM CONTROL PANEL Recommended type of cable Plain unscreened cable, 1.5mm Cable diameter ~ 2.5mm Transmission distance ≤1500m Contact capacity 30VDC@2A, 125VAC@0.5A FAULT OUT Recommended type of cable Plain unscreened cable, 1.5mm (COM, NO) Cable diameter ~ 2.5mm...
  • Page 5 ①CB-Board ② MB-Board ③Communication Board ④PMC_01 ⑤Switching Power Supply ⑥Buzzer ⑦Battery In general, the SEC1000 consists of 2 sections: 1. The left internal section contains the CB-Board, which integrated main processor, Buttons and LEDs, the I/O communication interface of MB-Board.
  • Page 6: Internal Wiring

    SEC1000 FIRE ALARM CONTROL PANEL communication board; The RS485 interface is reserved. 3.2 Internal wiring 250V 10A Blue Yellow&green Brown AC(TB1) AC(TB5) DC(TB2) LED(TB3) ADJ(TB4) SEC1000_CB SEC1000_MB SEC1000_COM PMC_01 LSP-75-24 RS485 Black Black Black Black Black 3.3 Mounting the chassis to the wall The panel can be surface or semi-flush mounted through the four mounting holes provided.
  • Page 7: Mains Connection

    SEC1000 FIRE ALARM CONTROL PANEL 3.4 Mains connection To connect the panel to the main power source, use a three-core cable with good quality cable glands fitted, and connect it to the P.S.E as the figure shows below. 250V 10A Blue Yellow&green...
  • Page 8: Points Connection To The Loop

    SEC1000 FIRE ALARM CONTROL PANEL Note: Do NOT connect batteries before applying mains power first. 3.6 Points connection to the loop The loop supports class A and Class B types. The figure in next page shows a typical Class A loop connection complete with detectors, sounder strobes, modules and loop isolators.
  • Page 9: Maximum Loop Cable Length Recommendations

    SEC1000 FIRE ALARM CONTROL PANEL 3.7 Maximum loop cable length recommendations To ensure a reliable system, some care must be taken when calculating the appropriate cable gauge for the system. The main limitation is that during an alarm condition (maximum current draw), the maximum volt drop at the end of the loop must be at least 19 Volts .
  • Page 10: Indications And Controls

    SEC1000 FIRE ALARM CONTROL PANEL 4. 24VK: It refers to a 24V power supply. It provides 24V output continuously and disconnects the power for about 4 seconds at the time the panel is reset. 4. Indications and Controls 4.1 LED indicators...
  • Page 11: Button Controls

    SEC1000 FIRE ALARM CONTROL PANEL 4.2 Button controls Gives an evacuation warning by activating all sounders of the system at access level 2&3 Returns the panel to its normal condition by clearing all fire and fault status indications at access level 2&3 Silences the system’s sounders at access level 2&3.
  • Page 12: Zone Indicators

    SEC1000 FIRE ALARM CONTROL PANEL Used to cancel a navigation step or exit the current menu For toggling, scrolling, or moving the input cursor ◄ ▼ ▲ ► Confirms a text input or a manual operation Used to enter numbers, letters and marks in a text box.
  • Page 13 SEC1000 FIRE ALARM CONTROL PANEL The SEC1000’s network protocol allows the interconnection of 20 SEC1000 main panels by CAN bus. To build a network, all panels should be registered on the central panel (Host No.1). Tick the ‘Share’ option if alarm signal of the central panel is required to be transmitted to the other sub panels.
  • Page 14: Bus Setup

    SEC1000 FIRE ALARM CONTROL PANEL 5.2.2 Bus setup All configurations and commissioning relating to the bus is set under the BUS category, including naming of zones, registering and assignment of detectors/modules, and reading of the system details. The sub-menus are as example below:...
  • Page 15 SEC1000 FIRE ALARM CONTROL PANEL Since the Product Type is an inherent attribute of a field device, the optional product types provided in this system are listed as follows. Ionization detector Optical detector Heat detector Strobe Infrared detector Combination detector...
  • Page 16: C&E Programming

    SEC1000 FIRE ALARM CONTROL PANEL Batch setup If several devices with consecutive addresses have same features to be set, an alternative to configuring them all individually is to make a batch set. Double-click the option title to be set or press direction buttons to select one column and press ENTER, the setup window then pops up.
  • Page 17 SEC1000 FIRE ALARM CONTROL PANEL The delay function only applies to the associated loop sounders. Under no circumstance will S.C.Out or F.A.Out be delayed when they are applicable. General c&e The programming window is as follow: It consists of two main parts: the Conditions (serve as the Causes) and the Outputs, which together can make a c&e rule.
  • Page 18: Disable/Test Functions

    SEC1000 FIRE ALARM CONTROL PANEL Specific c&e In this section, the Causes can apply to specific devices by entering their assigned addresses. Maximum of 5 points can be set at one time. Here the meaning of its c&e rule is only when all the points set in the conditions are active, the outputs could take place.
  • Page 19: Advanced Functions

    SEC1000 FIRE ALARM CONTROL PANEL The curve indicates the change of smoke density in the no.47 smoke detector during the test. Here, the background value, alarm value and drift value only apply to smoke detector. Press Exit to stop at any time.
  • Page 20 SEC1000 FIRE ALARM CONTROL PANEL When the time counted is over, the loop learn fails and it prompts timeout error. Save data to U-disk This function will copy the file of system configuration to the U-disk you insert at the top right USB port of the front panel.
  • Page 21: View System And Software Version Info

    SEC1000 FIRE ALARM CONTROL PANEL Restart the panel after it indicates the file reset completes. Update system The system allows to be updated on site with additional functions by using a U-disk at the authorized engineer level for future development. Copy the file needed to the U-disk and insert it to the USB port.
  • Page 22: Battery Capacity Calculation

    SEC1000 FIRE ALARM CONTROL PANEL 6. Battery Capacity Calculation The standby time of the fire alarm control panel after the main power source has failed depends on the quiescent load of the panel, the alarm load of the panel, and the capacity of the batteries.
  • Page 23: Troubleshooting

    SEC1000 FIRE ALARM CONTROL PANEL 7.2 Troubleshooting Solution of all suspected faults MUST only be carried out by suitably qualified technical engineers. Problem: apply power to the panel but the LCD display is off and panel does not work. ...
  • Page 24: Annex - Device Type List

    SEC1000 FIRE ALARM CONTROL PANEL Annex - Device type list Device Abbr. Ionization Detector IonDet Optical Detector OptDet Heat Detector HeatDet Infrared Beam Detector IRDet Combination detector (smoke and heat detector) CombDet Combustible Gas Detector GasDet JS Input Module JSInputM...
  • Page 25 SEC1000 FIRE ALARM CONTROL PANEL Door Holder DoorHolder Door Sensor/Magnetic Contact Switch DoorSensor Deluge Valve DelugeVal Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air-con Fire Emergence Evacuation Broadcast BCST Fire Emergency Lightning...
  • Page 26 SEC1000 FIRE ALARM CONTROL PANEL...

Table of Contents