SANJIANG SEC3002 Installation & Commissioning Manual

SANJIANG SEC3002 Installation & Commissioning Manual

Fire alarm control panel

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for SANJIANG SEC3002

  • Page 2: Table Of Contents

    SEC3002 FIRE ALARM CONTROL PANEL CONTENTS 1. About This Manual............................2 2. Introduction..............................2 2.1 Overview............................. 2 2.2 Technical Specifications........................2 3. Installation and Connections........................4 3.1 Panel’s interior........................... 4 3.2 Mounting the chassis to the wall....................5 3.3 Mains connection..........................5 3.4 Battery connection..........................6 3.5 Points connection to the loop......................6...
  • Page 3: About This Manual

    2. Introduction 2.1 Overview The purpose of the SEC3002 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.
  • Page 4 SEC3002 FIRE ALARM CONTROL PANEL 18.5 ~ 27.5VDC Output voltage Max. output current 0.5A Fuse rating F1AL250V F.P.E. Out (+, -) End of line resistor F.A. Out (+, -) Type of cable Plain unscreened cable, 1.5mm ~ 2mm Cable diameter ≤1500m...
  • Page 5: Installation And Connections

    ⑥P.S.E ⑦Battery ⑧PSE Filter ⑨Loop SPU (surge protective unit) ⑩Zone Indication and Control Panel ⑪LED_Button Board In general, the SEC3002 consists of 2 sections: 1. The right internal section contains the main processor of A-Board, the I/O communication interface of B-Board, the Buttons and LEDs Board, the ZCP board, the LCD and the Printer mounting area.
  • Page 6: Mounting The Chassis To The Wall

    SEC3002 FIRE ALARM CONTROL PANEL the LCD and the optional Communication Board; terminals of RS-485 and CAN bus for the communication between internal circuit boards. IO Board It generally contains terminals or interfaces for connecting the P.S.E, the internal B-Board, the loop devices, the Loop SPU, the additional loop board (if applicable) and other peripheral devices.
  • Page 7: Battery Connection

    SEC3002 FIRE ALARM CONTROL PANEL PSE Filter P.S.E AC power Yellow&Green Blue Brown BAT+ Black Brown To battery Blue Yellow&Green 3.4 Battery connection For this single loop system, 2×12V/17Ah sealed lead acid batteries are used as per the calculation of battery capacity in section 6. The batteries should be connected in series first using the link wire supplied and be located within the panel enclosure.
  • Page 8: Other Terminal Connections

    SEC3002 FIRE ALARM CONTROL PANEL 3.6 Other terminal connections 1. F.A. Out short for Fire Alarm Output: When there is a general fire the output is activated. A 4K7 end-of-line resistor (provided) is connected at the end of the circuit to allow the wiring to be monitored.
  • Page 9: Indications And Controls

    SEC3002 FIRE ALARM CONTROL PANEL is also monitored for open and short circuit fault of its wiring. A typical connection is shown below. 4. S.C. Out short for Sounder Circuit Output: A conventional sounder circuit is provided. When there is a general fire it activates the sounders connected by default. The sounders can be aborted and restarted by pressing the SILENCE/RESOUND button.
  • Page 10: Button Controls

    SEC3002 FIRE ALARM CONTROL PANEL DISABLE Lit yellow when one or more loop devices, zones or outputs are disabled POWER FAULT Lit yellow when the panel’s mains power, battery or charger is in fault condition DELAY Steadily lit yellow when delay is configured as part of one or more cause and effect rules.
  • Page 11: Zone Indication And Control Panel

    SEC3002 FIRE ALARM CONTROL PANEL EVAC Gives an evacuation warning by activating all sounders of the system at access level 2&3 F.P.E. DIS/EN Disables or re-enables the F.P.E. Out at access level 2&3 SILENCE/RESOUND Silences the system’s sounders at access level 2&3. Press...
  • Page 12: Functions Available At Access Level 3

    Select the network setup option under the menu category of SYSTEM, the following window (or similar) will appear. The SEC3002’s network protocol allows the interconnection of 20 SEC3002 main panels by CAN bus. To build a network, all panels should be registered on the central panel (Host No.1).
  • Page 13: Bus Setup

    The FIP (fire indicating panel, also called as ‘repeater’) is a displaying terminal unit in the system showing alarm messages by connecting to the SEC3002 control panel through the RS-485 bus. It has two working modes: display all the alarm messages from the control panel, or only the messages of the zone where it is assigned to.
  • Page 14 SEC3002 FIRE ALARM CONTROL PANEL Zone setup When this menu option is selected, a window is shown to allow you to register and add a description for a specific zone, and to configure the ‘Resound’ option. The ‘Resound’ function is selected...
  • Page 15: C&E Programming

    SEC3002 FIRE ALARM CONTROL PANEL Here, the device following the output module of address no.1 is an electromagnetic valve. The Device Type is a concept specially defined for module devices, which refers to the type of device a module connects with. For example, the Device Type of an output module could be fire door, blow valve, etc.
  • Page 16 SEC3002 FIRE ALARM CONTROL PANEL Click by the USB mouse or press ► to select the C&E menu option. It shows 5 sub-menus: Default c&e delay A default output is designed for the sake of c&e setting brevity, that is, the associated zonal sounder, F.A.Out, F.P.E.Out and S.C.Out (if applicable) will be activated when a fire occurs.
  • Page 17 SEC3002 FIRE ALARM CONTROL PANEL The meaning of this c&e is when any 2 of smoke detector, heat detector or manual call point are active, the electromagnetic valve wired after the I/O module with the address of 155 will be triggered after 10s.
  • Page 18: Disable/Test Functions

    SEC3002 FIRE ALARM CONTROL PANEL 5.2.4 Disable/test functions Besides the disable/test functions that can be carried out at access level 2, there are some other tests designed specially for the convenience of commissioning by authorized personnel at access level 3. They are point test, module start/stop and duplicate address check.
  • Page 19: Advanced Functions

    SEC3002 FIRE ALARM CONTROL PANEL 5.2.5 Advanced functions Besides some essential system configurations mentioned above, this ADVANCE category provides supplementary functions for system commissioning including loop learn, data load/backup, file reset and update of the system. Loop learn This function activates the panel’s automatic loop learn facility. As it prompts below, the loop learn process may take about 120s and it cannot be stopped during the period.
  • Page 20: View System And Software Version Info

    SEC3002 FIRE ALARM CONTROL PANEL Take the prompt as reference: Press ‘Yes’ to start copy. The process might take about 30-60s and other function will be suspended. Load data from U-disk This function will load the configuration file from U-disk to the panel’s flash and overwrite the panel’s existing data.
  • Page 21: Battery Capacity Calculation

    SEC3002 FIRE ALARM CONTROL PANEL through the corresponding menu options under the category of ‘LOG’. System information Software versions The version for each program of the control panel can be identified under this window. Meanwhile, there will be a label regarding the version stuck on or beside each processor for convenience.
  • Page 22: Maintenance And Troubleshooting

    SEC3002 FIRE ALARM CONTROL PANEL is the amount of standby hours required (most commonly being 24 hours); is the amount of alarm hours required (most commonly being half an hour). Take the system of 324 points with a printer as an example: there are 312 addressable detectors, 12 input/output modules, 12 conventional sounder strobes, 12 loop isolators and 3 full loaded relay output.
  • Page 23 SEC3002 FIRE ALARM CONTROL PANEL Problem: the F.P.E.Out, the F.A.Out, or the S.C.Out is reported fault.  Possible reason and solution: ensure that a 4K7 EOL resistor is well connected to each of the three ports; Check if the corresponding fuse of F2, F3 or F4 on the IO board blows out; Check if the jumper of JP3, JP6 or JP10 beside the fuse is slipped over the pins accordingly.
  • Page 24: Annex - Device Type List

    SEC3002 FIRE ALARM CONTROL PANEL Annex - Device type list Device Abbr. Ionization Detector IonDet Optical Detector OptDet Heat Detector HeatDet Infrared Beam Detector IRDet Combination detector (smoke and heat detector) CombDet Combustible Gas Detector GasDet JS Input Module JSInputM...
  • Page 25 SEC3002 FIRE ALARM CONTROL PANEL Door Sensor/Magnetic Contact Switch DoorSensor Deluge Valve DelugeVal Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air-con Fire Emergence Evacuation Broadcast BCST Fire Emergency Lightning EmLight...