Series 19 SMART Modulating Electric Actuator User Manual
The Series 19 smart modulating electric actuator features a reversing motor with multi-
voltage capabilities, 95 VAC to 265 VAC (50/60 Hz) or 24 VAC/VDC, an OLED screen,
an internal heater, positioner, transmitter, alarm/fault contacts, a NEMA Type 4X
enclosure, manual override, visual beacon position indication, LED fault indicator (blue),
ISO mounting, and flying leads. The alarm/fault contacts are SPST and rated for 0.1
Amp @ 250 VAC/0.5 Amp @ 30 VDC, and are factory calibrated.
Cover removal is NOT required for installation and will void warranty!!
Additional options are NOT available for this model.
WARNING: Do not open actuator cover as warranty will be void!!
Model Number
S20HC1C3W
S50HC1C3W
S110HC1C3W
NOTE: Amp rating is considered running.
Duty cycles are for ambient temperature (73° F)
The Series 19 electric actuator has a sealed cable gland with 2 meter flying leads. The
electrician is required to make field connections as per the wiring schematic shown in
this manual for model numbers and voltages listed above. The electrician is responsible
for following all and any, local and/or agency wiring practices.
Note: Not all wires provided will be used.
Heater is internally wired and operational as long as actuator is powered.
Need more information? Download a complete IOM at our website.
File: Series 19 SMART Modulating User Manual

Description

Electrical Requirement

95 VAC to 265
VAC
Torque
(in-lbs)
Amp
Duty
Draw
Cycle
177
0.18
75%
442
0.24
75%
973
0.84
75%
24 VAC/24
Cycle Time
VDC
per 90
Amp
Duty
Degrees
Draw
Cycle
(Seconds)
0.96
75%
10 seconds
1.20
75%
10 seconds
4.80
75%
10 seconds
www.asahi-america.com
Rev C
11/3/2022
Weight
(Pounds)
1.7
3.5
4.8
Page 1 of 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S20HC1C3W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Asahi/America S20HC1C3W

  • Page 1 90 Weight Model Number (in-lbs) Duty Duty Degrees (Pounds) Draw Cycle Draw Cycle (Seconds) S20HC1C3W 0.18 0.96 10 seconds S50HC1C3W 0.24 1.20 10 seconds S110HC1C3W 0.84 4.80 10 seconds NOTE: Amp rating is considered running. Duty cycles are for ambient temperature (73° F) The Series 19 electric actuator has a sealed cable gland with 2 meter flying leads.
  • Page 2 Size 20 ONLY Size 20 is specific to accept only voltage or current as a control signal/loop Size 20 will be labelled specifically as a voltage or current control signal/loop, and cannot be changed via onboard firmware. If a different control signal/loop is required, then another unit with the specific control signal/loop must be used.
  • Page 3 Size 50 – 110 Size 50 – 110 can be calibrated for EITHER a voltage or a current control signal/loop via onboard firmware. Please contact the factory for instructions. Manual Override Operation Remove manual override hex key from storage position located on the bottom of actuator, which is secured by stainless clips.
  • Page 4 to open, CW to close). When finished using the manual override, it is imperative to remove the hex key and place it back into storage on actuator base, making sure that it “clicks” into the locking position. CAUTION: The manual override should only be used when there is no power applied to actuator.
  • Page 5 Confirm that control signal wiring is terminated at the appropriate wiring Crossed signal wiring location of actuator (0-10 VDC signal connected to 4-20 mA actuator wiring, as an example) Series 19 ISO 5211 Output Series 19 Envelope Dimensions Need more information? Download a complete IOM at our website. www.asahi-america.com File: Series 19 SMART Modulating User Manual Rev C...

This manual is also suitable for:

19 smart seriesS50hc1c3wS110hc1c3w