Carrier 020-093 Installation, Operation And Maintenance Instructions page 56

Packaged rooftop units
Table of Contents

Advertisement

12 - FACTORY OPTIONS AND ACCESSORIES
■ Fuel
Before starting up the heater, make sure that:
- the gas mains supply data is compatible with the data stated
on the nameplate;
- the combustion air intake ducts (when fi tted) and the fume
exhaust pipes are those specifi ed by the manufacturer;
- the combustion air is supplied in such a way as to avoid even
partial obstructions of the intake grille (caused by leaves etc.);
- the fuel intake internal and external seal is checked during
the testing stage, as required by applicable standards;
- the burner is supplied with the same type of fuel it has been
designed for;
- the system is correctly sized for such fl ow rate and is fi tted
with all safety and monitoring devices required by applicable
standards;
- the inside of the gas pipes and air distribution ducts for ducted
heaters has been thoroughly cleaned;
- the fuel fl ow rate is suitable for suitable for the power required
by the burner;
- the fuel supply pressure is between the range specifi ed on
the nameplate.
If the burner is not going to be used over a prolonged
period the gas supply valve must be closed.
■ Gas leaks
If there is gas smell:
- do not operate electrical switches, telephones or any other
object or device that could produce sparks;
- immediately open doors and windows to create an air fl ow
to vent the gas out of the room;
- close the gas valves;
- call for qualifi ed staff.
Supplying the gas circuit with pressure higher
than 60 mbar is strictly prohibited. Such pressures
could cause the valve to break.
■ Operation
Do not allow children or inexperienced people to use any
electrically powered equipment.
The following instructions must be followed:
- do not touch the equipment with wet or damp parts of your
body and/or with bare feet;
- do not leave the equipment exposed to the elements (rain,
sun etc....) unless it is adequately protected;
- do not use the gas pipes to earth electrical equipment;
- do not touch the hot parts of the heater, such as the fume
exhaust duct;
- do not wet the heater with water or other fl uids;
- do not place any object over the burner;
- do not touch the moving parts of the burner.
■ Maintenance
Maintenance operations and combustion inspections must
be carried out in compliance with current standards.
Before carrying out any cleaning and maintenance operations,
isolate the heater from the mains power supply from the switch
located on the electrical system and/or on the shut-out devices.
56
If the heater is faulty and/or incorrectly operating, switch it off
and do not attempt to repair it yourself, but contact our local
Technical Service.
All repairs must be carried out by using genuine spare parts.
Failure to comply with the above instructions could compromise
the safety of the equipment and invalidate the warranty.
If the equipment is not used for long periods, shut the gas
upply off through the gas stopcock and disconnect it from the
power supply.
If the heater is to be put out of service, in addition to the above
operations, potential sources of hazard on the unit must be
removed.
It is strictly forbidden to obstruct the Venturi pipe inlet, located
on the burner-fan unit, with your hands or with any other objects.
Any obstruction could cause a backfi re from the premixed
burner.
General recommendations
■ Country table - gas category:
Country
Category
Austria,
II2H3B/P
Switzerland
Belgium
I2E(S)
<70kW
B,I3P
Belgium
I2E(R)
>70kW
B,I3P
Germany
II2ELL3B/P G20/G25
Denmark,
Finland,
Greece,
Sweden,
Norway,
Italy,
Czech
Republic,
Estonia,
II2H3B/P
Lithuania,
Slovenia,
Albania,
Macedonia,
Bulgaria,
Romania,
Croatia,
Turkey
Spain,
United
Kingdom,
II2H3P
Ireland,
Portugal,
Slovakia
France
II2Esi3P
Luxembourg II2E3P
Netherlands II2EK3B/P
Hungary
II2HS3B/P
Cyprus,
I3B/P
Malta
Latvia
I2H
Iceland
I3P
II2ELwLs-
Poland
3B/P
Russia
II2H3B/P
(*) Consult the available burners with G2.350.
Gas
Pressure
Gas
(mbar)
G30/
G20
20
G31
G20/G25
20/25
G31
G20/G25
20/25
G31
G30/
20
G31
G30/
G20
20
G31
G20
20
G31
G20/G25
20/25
G31
G20/G25
20
G31
G20/
G30/
20/25
G25.3
G31
G20/
G30/
25
G25.1
G31
G30/
--
--
G31
G20
20
--
--
G31
G20/G27/
G30/
20/13
G2.350 (*)
G31
G30/
G20
20
G31
Pressure
(mbar)
50
37
37
50
30
37
37
37/50
30
30
30
37
37
30

Advertisement

Table of Contents
loading

This manual is also suitable for:

50fc50ff020-099

Table of Contents