Riello C9161400 Installation, Use And Maintenance Instructions page 31

Dual fuel light oil/ gas burners progressive two stage or modulating operation
Table of Contents

Advertisement

Duct expansion and contraction can be managed by using two
relatively long duct runs that are 90° apposed to each other.
A small movement in the angle between these two legs will pro-
vide the space needed to absorb the expansion and contrac-
tion. The ends of the FGR duct must be securely attached to
allow this to work properly, and prevent high loads from being
applied to the burner or stack.
A condensation drip leg must be provided upstream of the FGR
control valve and the FGR shutoff valve (if used). There must
be sufficient condensate drip legs and catch space (volume of
drip legs) to prevent the condensation from flowing through the
control valves and into the fan.
In cases of heavy condensation, a condensate drip leg may be
required on the bottom of the housing, to remove condensate.
Determine if pipe reducers are needed for the connection to the
FGR control valve and the FGR shutoff valve.
The duct must be properly supported, handling both the weight
of the duct and to control the thermal expansion and contrac-
3
6
7
D11299/S8367
1
Key (Fig. 23)
1
Primary gas supply inlet
2
Inducted FGR modulating damper
3
Flue gas recirculation pipe
4
Boiler stack
5
Alternate Construction Using "T"
6
Burner
7
Boiler
8
Drain Valve (Manual Ball Valve, Stainless Steel)
9
Drain line
10 Condensate Trap
Installation
tion. The supports may need to be anchored to provide this sta-
bility in the FGR duct.
CAUTION
The FGR duct is normally made from schedule 40 pipe be-
cause it is easily obtainable and inexpensive.
Schedule 20 pipe can also be used for this application.
The duct components must be seal welded, flanged or screwed
together to provide an air tight duct.
Air leakage into the duct will prevent the system from working
properly. It is sufficient to only inspect the welds for a proper
seal, they do not need to be leak tested.
4
8
9
29
GB
Uncontrolled condensation can cause premature
failure of the control valves, fan and motor.
Adequate means must be provided to remove con-
densation from the system.
Cold startup will generate significant amounts of
condensation.
2
10
3
5
8
8
Fig. 23
20037168

Advertisement

Table of Contents
loading

Table of Contents