Troubleshooting
Table 13-3 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
O
S
F
(will require a manual
One or both of the outlet sensors has
reset once the condition
opened or shorted.
has been corrected.
Press the RESET
button on the display to
reset.)
I
S
F
(will require a manual
reset once the condition
The inlet sensor is open.
has been corrected.
Press the RESET
button on the display to
reset.)
S
P
M
The temperature has reached the set point
+ 10°F.
The main control board has received a call
A
-C
for heat too quickly after the previous call for
heat has ended.
The temperature rise across the heat
exchanger has exceeded the set parameters
for the boiler.
D
T H
The fan speed is being limited due to the
temperature rise across the heat exchanger
exceeding 55°F.
(continued)
DESCRIPTION
Installation & Service Manual
F I R E T U B E
CORRECTIVE ACTION
• Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
• Measure the resistances of the sensors and compare
the resistances to the tables on page 83. Replace if
necessary.
• Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
• None
• The control board will release the call for heat after 60
seconds.
• The control board will release the call for heat if the
outlet temperature drops 10°F.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system.
Refer to Section 6 - Hydronic Piping
for the proper piping methods for the Lochinvar Combi
Boiler.
• Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• Verify that the boiler pump is set to the proper speed
or that the pump is the proper size.
Section
6
-
Hydronic
pump specifications.
Reference
Piping
for
boiler
89